Sicherheitshinweise

Sicherheitshinweise für die Installation nach UL oder UR

2

l

11

EDK94ARN24 DE/EN/FR/ES/IT 2.1

2.3

Sicherheitshinweise für die Installation nach U

L

oder U

R

J

Warnings!

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V max.

ƒ

Voltage of the fuses must at least be suitable with the input voltage of the
drive. Branch circuit short circuit protection with fuses in accordance to
UL248.

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

Use 60 °C copper wire only for power circuits.

ƒ

Use 75 °C copper wire only for 24 V DC control circuits of filter, except for
other control circuits.

Branch circuit protection

Type

Fuse [A]

E94ARNE0134

30

E94ARNE0244

60