Outputs_analog1 (analog output), Drive plc, System blocks – Lenze Global Drive PLC Developer Studio User Manual

Page 35: 2 outputs_analog1 (analog output)

Advertising
background image

Drive PLC

System blocks

2.6

ANALOG1_IO (node number 11)

2−21

L

DrivePLC DE 6.0

2.6.2

Outputs_ANALOG1 (analog output)

You can use this SB as a monitor output. You can output internal analog signals via

·

terminal AOV as voltage signals and

·

terminal AOI as current signals

and use them, e.g. as display or setpoint values for following drives.

AOV

A

AOUT1_nOut_a

Outputs_ANALOG1

C0434

AOI

Fig. 2−11

Outputs_ANALOG1

System variables

Variable

Data type

Signal type

Address

Display

code

Display

format

Notes

AOUT1_nOut_a

Integer

analog

%QW11.0

C0434

dec [%]

Analog output 1

Function

·

A voltage of 10 V is output at terminal AOV, if the signal on AOUT1_nOut_a = 16384 = 100 %

·

A current of 20 mA is output at terminal AOI, if the signal on AOUT1_nOut_a = 16384 = 100 %

Terminal assignment

Terminal

Use

Data

AOV

Analog output 1 (voltage signal)

Level:
Resolution:
Normalisation:

−10 V ... +10 V (max. 2 mA)
10 bits + sign
±10 V º ±16384 º ±100 %

AOI

Analog output 1 (current signal)

Level:
Resolution:
Normalisation:

−20 mA ... +20 mA
10 bits + sign
±20 mA º ±16384 º ±100 %

A

^

Internal ground, GND