DCa180SSI/DCa180SSIu 60 hz gen/ • operaTIon anD parTS manual — rev. #1 (08/02/10) — page 29

OUtpUt terMinaL paneL cOnnectiOns

3Ø-480v uvWo Terminal output voltages

1. Jumper the voltage change-over board for 480V

operation as shown in Figure 24. This configuration

uses 6 jumper plates in 3 different positions. Remember

there are 2 jumper plates at every position. Every

jumper plate

must be used.

Figure 24. Voltage Change-Over Board 480V

Configuration

2. Connect the load wires to the UVWO terminals as

shown in Figure 25.

Figure 25. UVWO Terminal Lugs 3Ø-480V

Connections

NOTICE

alWaYS make sure that the connections to the UVWO

terminals are

secure and tight. The possibility of arcing

exists, that could cause a fire.

1Ø-480v uvWo Terminal output voltages

1. Make sure the voltage change-over board is jumpered

for 480V operation as shown in Figure 24.

2. Connect the load wires to the UVWO terminals as

shown in Figure 26.

Figure 26. UVWO Terminal Lugs 1Ø-480V

Connections

1Ø-277v uvWo Terminal output voltages

1. Make sure the voltage change-over board is jumpered

for 480V operation as shown in Figure 24.

2. Connect the load wires to the UVWO terminals as

shown in Figure 27.

Figure 27. UVWO Terminal Lugs 1Ø-277V

Connections