page 36 — DCa180SSI/DCa180SSIu 60 hz gen. • operaTIon anD parTS manual — rev. #1 (08/02/10)

generatOr start-Up prOceDUre (aUtO MODe)

Figure 51. Ammeter (Load)

15. The generator will run until manually stopped or an

abnormal condition occurs.

STarTIng (auTo moDe)

Danger

Before connecting this generator to any

building’s electrical system, a

licensed

electrician must install an isolation

(transfer) switch. Serious damage to

the building’s electrical system may occur without this

transfer switch.

CauTIon

When connecting the generator to a isolation (transfer)

switch,

alWaYS have power applied to the generator’s

internal battery charger. This will ensure that the engine

will not fail due to a dead battery.

NOTICE

When the generator is set in the

auTo mode, the

generator will

automatically start in the event of

commercial power falling below a prescribed level

by means of a contact closure that is generated

automatically by a transfer switch.

WarnIng

When running the generator in the

auTo mode,

remember the generator can start up at any time without

warning.

never attempt to perform any maintenance

when the generator is in the auto mode.

CauTIon

The engine speed switch

must be set to the “High”

position when running in the

auto-start mode. Failing

to set the switch in the proper position can result in

damage to your generator when it turns on.

NOTICE

When the MPEC control switch is placed in the

auTo

position, the engine glow plugs will be warmed and the

engine will start automatically.