Operating procedure – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 91

Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-21
.
Alarms
It will be specified in this section when an alarm must be assigned (i.e., when
an alarm must be set) for the Control Output 1 or 2 Assignment parameters,
or for the Auxiliary Output 1 or 3 Assignment parameters. For example, if
alarm 1 is set for the Control Output 1 Assignment parameter, then alarm 1
has been assigned.
EXAMPLE
Operating Procedure
The following example configures the following control and auxiliary out
assignments: Control Output 1: Control Output (Heating); Control Output 2:
Table 3.F — 900-TC8 and 900-TC16
Parameter
Name
Symbol
Without Control Output 2
With Control Output 2
Standard
Heating/
Cooling
Standard
Heating/
Cooling
Control Output 1
Assignment
out 1
Control output
(heating)
Control
output
(heating)
Control
output
(heating)
Control
output
(heating)
Control Output 2
Assignment
out 2
Not assigned
➊
Not
assigned
➊
Not
assigned
Control
output
(cooling)
Auxiliary Output
1 Assignment
sub 1
Alarm 1
➋
Alarm 1
➋
Alarm 1
➋
Alarm 1
➋
Auxiliary Output
2 Assignment
sub 2
Alarm 2
➌
Control
output
(cooling)
➌
Alarm 2
➌
Alarm 2
➌
➊ There is no control output 2 and no parameter assignment is displayed for that output.
➋ The Auxiliary Output 1 Assignment parameter becomes the program end output unless the Program
Pattern parameter is configured to OFF.
➌ For the 900-TC8, the Auxiliary Output 3 Assignment parameter is set as the control output for cooling.
(The Auxiliary Output 2 Assignment parameter is set for alarm 2).
Table 3.G — 900-TC32
Parameter Name
Symbol
Standard
Heating/Cooling
Control Output 1
Assignment
out 1
Control output
(heating)
Control output
(heating)
Auxiliary Output 1
Assignment
sub 1
Alarm 1
➋
Control output
(cooling)
➋ The Auxiliary Output 1 Assignment parameter becomes the program end output unless the
Program Pattern parameter is configured to OFF.