Programming – Rockwell Automation 1336R REGEN LINE REG User Manual
Page 92

3–40
Regenerative Brake Operation
Programming
Parameter No.
27
Display Units
Bits
Parameter Type
Read/Write
Factory Default
XXX11100
Min/Max Value
N/A
Drive Units
N/A
Fault Select 1
This parameter enables or disables faults as defined by the first (5) bits of a (16) bit word. The
[Fault Select1] parameter may be set while the 1336 REGEN Converter is enabled.
Parameter No.
28
Display Units
Number
Parameter Type
Read/Write
Factory Default
5
Min/Max Value
1/32
Drive Units
N/A
HIM Default Display Parameter
This parameter sets which of the previous parameters will be displayed after 1336 REGEN
Converter power-up. The [HIM Display Param] parameter may be set while the 1336 REGEN
Converter is enabled.
S e l e c t 1
a u l t
F
0 0
2 7
1
X X 1 1
X
Bit 2
Bit 1
Bit 0
0 = SCANport 1 Timeout Disabled
1 = SCANport 1 Timeout Enabled
0 = SCANport 2 Timeout Disabled
1 = SCANport 2 Timeout Enabled
0 = Phase Mismatch Fault Disabled
1 = Phase Mismatch Fault Enabled
0 = Open Precharge Fuse Fault Disabled 1 = Open Precharge Fuse Fault Enabled
0 = PLL Fault Disabled
1 = PLL Fault Enabled
Bit 3
Bit 4
s p l a y P r m
i
I M D
H
5
2 8