Network status
Off
The device is not initialized or the module does not
have an IP address.
Flashing green
The device has no CIP connections.
The device has an IP address, but no CIP connections
are established.
Green
The device is online, has an IP address, and CIP
connections are established.
Flashing red
One or more connections have timed out.
Red
The module has detected that its IP address is already
in use.
Flashing red/green
The module is performing a powerup self-test.
Network link status
Off
No link established.
Green
Link established on indicated port at 100 Mbps.
Flashing green
Link activity present on indicated port at 100 Mbps.
Yellow
Link established on indicated port at 10 Mbps.
Flashing yellow
Link activity present on indicated port at 10 Mbps.
Power status
Off
No power to device or input not valid.
Green
Power applied to device.
Digital output status
Off
Output not energized.
Yellow
Output energized and output power applied.
Flashing yellow
Output energized and no output power.
Red
(1)
Output shorted.
Flashing red
Output open load.
Digital input status
Off
No valid input.
Yellow
Valid input.
Red
(1)
Sensor source voltage shorted.
Flashing red
Sensor source open wire.
(1)
Only diagnostic modules 1732E-12X4M12QCDR and 1732E-12X4M12P5QCDR have red I/O status LED indicators.
IMPORTANT
In non-QuickConnect mode, the Module Status LED indicator flashes red
and green for a maximum 5 s while the module completes its POST
(Power-On Self Test).
Indicator Status for Modules
Status
Description