Rockwell Automation 1769-IF8 Compact 1769-IF8 Analog Input Module User Manual
Page 26

26 Compact I/O 1769-IF8 Analog Input Module
Publication 1769-IN067B-EN-P - September 2005
Specification
1769-IF8
Accuracy Drift with Temperature
Voltage Terminal: ±0.003% per °C
Current Terminal: ±0.0045% per °C
Calibration
The module performs autocalibration on channel enable and on a
configuration change between channels.
Non-linearity (in percent full scale) ±0.03%
Repeatability
(1)
±0.03%
Module Error over Full
Temperature Range
(0 to +60°C [+32°F to +140°F])
Voltage: ±0.3%
Current: ±0.5%
Input Channel Configuration
via configuration software screen or the user program (by writing a unique
bit pattern into the module’s configuration file). Refer to your controller’s
user manual to determine if user program configuration is supported.
Module OK LED
On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.
Channel Diagnostics
Over- or under-range by bit reporting, process alarms
Maximum Overload at Input
Terminals
(2)
Voltage Terminal: ±30V dc continuous, 0.1 mA
Current Terminal: ±32 mA continuous, ±7.6 V dc
System Power Supply Distance
Rating
8 (The module may not be more than 8 modules away from the system
power supply.)
Recommended Cable
Belden™ 8761 (shielded)
Input Group to Bus Isolation
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
1
Product Type Code
10
Product Code
38
(1)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
(2)
Damage may occur to the input circuit if this value is exceeded.