Chapter 5
Add, Configure, Monitor, and Replace CIP Safety I/O
•
Configuration signature
See page
for information on when the configuration signature is set
automatically and when you need to set it.
•
Reaction time limit
for information on setting the reaction time limit.
•
Safety input, output, and test parameters
You can configure CIP Safety I/O modules via the Compact GuardLogix
controller by using RSLogix 5000 software.
Configure CIP Safety I/O
Modules via RSLogix 5000
Software
Add the CIP Safety I/O module to the communication module under the I/O
Configuration folder of the RSLogix 5000 project. Use a 1768-ENBT module,
revision 3 or later, for EtherNet/IP modules.
1.
Right-click the network and choose New Module.
2.
Expand the Safety category and choose a CIP Safety I/O module.
3.
Specify the module properties.
a. Modify the Module Definition settings, if required, by clicking
Change.
b. Type a name for the new module.
c. Enter the IP address of the module on its connecting network.
d. Modify the safety network number (SNN), if required, by clicking the
button.
See page
for details.
TIP
Safety I/O modules support standard and safety data. Module
configuration defines what data is available.
TIP
You cannot add or delete a CIP Safety I/O module while online.