Add, Configure, Monitor, and Replace CIP Safety I/O
Scenario 2 - Replacement Module SNN is Different from Original and Safety Signature Exists
1.
Remove the old I/O module and install the new module.
2.
Right-click your POINT Guard I/O module and choose Properties.
3.
Click the Safety tab.
4.
Click Reset Ownership.
5.
Click OK.
6.
Right-click your controller and choose Properties.
7.
Click
to the right of the safety network number to open the Safety
Network Number dialog box.