Calibrate the ControlLogix Isolated Analog I/O Modules
Chapter 8
4.
On the Configuration tab, make sure the Output Type for each channel to
be calibrated is set to Current (mA).
5.
On the Calibration tab, click Start Calibration.
6.
When the warning appears, click OK.
7.
Select the channels to be calibrated and click Next.