Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 179
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
179
Isolated Analog I/O Module Tag Definitions
Appendix A
Ch[x].CalGoodHighRef
BOOL
Indicates that a valid High Reference signal has been
sampled on this channel.
• 0 = Valid High Reference signal
has not been sampled on this
channel
• 1 = Valid High Reference signal
has been sampled on this
channel
Ch[x].CalBadHighRef
BOOL
Indicates that an invalid High Reference signal has been
sampled on this channel.
You must correct this condition to successfully calibrate
the module.
If calibration is aborted with an invalid High Reference
signal, the I.Ch[x].CalibrationFault tag is set for this
channel until a successful calibration is performed.
• 0 = Invalid High Reference
signal has not been sampled on
this channel
• 1 = Invalid High Reference
signal has been sampled on this
channel
Ch[x].CalSuccessful
BOOL
Indicates calibration on this channel is complete and the
Calibrating state has been exited.
This tag remains set after valid calibration as long as
connection is open.
• 0 = Calibration was not
successful
• 1 = Calibration was successful
and calibrating state has been
exited.
Ch[x].RateOfChange
REAL
Change in channel data since last sample in
Engineering Units/Second.
Value representing the rate
of change
0.0 = default (This value indicates
no change occurred since sample.)
Ch[x].Data
REAL
Channel data in scaled Engineering Units.
Any positive or negative value.
Determined by how you set the
scaling parameters on the channel.
For more information, see
Timestamp
DINT[2]
64-bit timestamp indicating when all 8 channels were
last sampled in terms of CIPSync time.
CIPSync Timestamp data
RollingTimestamp
DINT
16-bit timestamp that ‘rolls’ from 0…32,767 ms.
Compatible with existing PID/PIDE instructions to
automatically calculate sample deltas. With this module,
this PID/PIDE instruction uses the RPI because there is no
RTS available.
For more information on the Rolling Timestamp, see
0…32,767 ms;
where 1 ms = 1 count
Table 21 - 1756-IF8I Module - Input Tags
Tag Name
Size
Definition
Valid Values