5-2 Diagnose Problems
Indication
Probable Cause
Recommended Action
Network Status
Off
Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Apply power to device.
Flashing Green
Device is online but has no connections in the established state.
None - device is in Idle or Program mode.
Solid Green
Device is online and has connections in the established state.
None
Flashing Red
One or more I/O connections are in timed-out state.
Check for module failure and correct as
needed.
Solid Red
Critical link failure is present with failed communication device.
Device detected error that prevents it communicating on the
network.
Verify that adapter and terminal bases are
properly installed, and reinstall, as needed.
Flashing
Red/Green
Communication faulted device - the device detected a network
access error and is in communication faulted state. Device
received and accepted an Identify Communication Faulted
Request - long protocol message.
Verify that adapter is properly installed, and
reinstall, as needed.
Indication
Probable Cause
Recommended Action
Run Status
Off
Module is commanded to stop retrieving SSI data.
Turn Run on to begin collecting SSI data.
Solid Green
Module is commanded to retrieve SSI data.
None
Up Status
Off
SSI data is not increasing, or no SSI data is being received.
None
Solid Green
SSI data is increasing.
None
Down Status
Off
SSI data is not decreasing, or no SSI data is being received.
None
Solid Green
SSI data is decreasing.
None
Comp Status
Off
Comparator function is not in use, or comparator value not
attained.
None
Solid Green
Comparator value is attained.
None
I1 Status
Off
Latching input I1 is OFF.
None
Solid Yellow
Latching input I1 is ON.
None