Figure 2.27 sho, Figure 2.27, Important – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 48

Publication GMSI10-UM013D-EN-P - May 2010
38 Installing the XM-122 gSE Vibration Module
Figure 2.27 IEPE Accelerometer and Non-Contact Sensor Wiring
IMPORTANT
The internal transducer power supply is providing power to
the non-contact sensor.
IMPORTANT
A jumper from terminal 5 to terminal 6 is required for
channel 1 buffered output. A jumper from terminal 22 to
terminal 21 is required for channel 2 buffered output. Refer
to Configuring Buffered Output Input Range on page 28.
TYPICAL WIRING FOR IEPE ACCELEROMETER AND
NON-CONTACT SENSOR TO XM-122 VIBRATION MODULE
Shield
Pin A - Signal
Pin B - Common
Cable shield not
connected at this end
0
16
22
6
21
Channel 1 Input Signal
Signal Common
5
37
SIG
-24
COM
17
1
Signal Common
Channel 2 Input Signal
-24V DC
13
Shield
S hield Floating
Isolated Sensor Driver
*
*
*Note: Jumpering terminal 5 to terminal 6
configures CH 1 buffer (-5V to +24V)
Jumpering terminal 21 to terminal 22
configures CH 2 buffer (-24V to +9V)