Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual
Page 64
CE Conformity
64
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Table 5 PowerFlex 70 – EN61800-3 EMC Compatibility
Table 6 PowerFlex 70 – EN61800-3 First Environment Restricted Distribution
)
Table 7 PowerFlex 700 EN61800-3 EMC Compatibility
(1)
(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment
installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258
and FN258 models are recommended. Refer to
and
(2) Two turns of the blue comm option cable through a Ferrite Core (Frames A, B, C Fair-Rite #2643102002, Frame
D Fair-Rite #2643251002 or equivalent).
(3) Refer to the 1321 Reactor and Isolation Transformer Technical Data publication, 1321-TD001x for 1321-Mxxx
selection information.
Fr
am
e
Drive Description
Second Environment
Restrict Motor Cable
to 40 m (131 ft.)
Internal Filter
Option
External
Filter
(1)
Input
Ferrite
(2)
A
Drive Only
✔
–
✔
–
Drive with any Comm Option
✔
–
✔
–
Drive with Remote I/O
✔
–
✔
✔
B
Drive Only
✔
✔
–
–
Drive with any Comm Option
✔
✔
–
–
Drive with Remote I/O
✔
✔
–
✔
C
Drive Only
✔
–
–
–
Drive with any Comm Option
✔
–
–
–
Drive with Remote I/O
✔
–
–
✔
D
Drive Only
✔
–
–
–
Drive with any Comm Option
✔
–
–
–
Drive with Remote I/O
✔
–
–
✔
E
Drive Only
✔
–
–
–
Drive with any Comm Option
✔
–
–
–
Drive with Remote I/O
✔
–
–
✔
Fram
e
Drive Description
First Environment Restricted Distribution
Restrict Motor
Cable to:
Internal
Filter Option
External
Filter
(1)
Comm Cable
Ferrite
(2)
Common Mode
Core
(3)
A
Drive Only
40 m (131 ft.)
–
✔
–
–
Drive with any Comm Option
40 m (131 ft.)
–
✔
–
–
Drive with Remote I/O
40 m (131 ft.)
–
✔
✔
–
B
Drive Only
12 m (40 ft.)
✔
–
–
–
Drive with any Comm Option
12 m (40 ft.)
✔
–
–
–
Drive with Remote I/O
12 m (40 ft.)
✔
–
✔
–
C
Drive Only
12 m (40 ft.)
–
–
–
✔
Drive with any Comm Option
12 m (40 ft.)
–
–
–
✔
Drive with Remote I/O
12 m (40 ft.)
–
–
✔
✔
D
Drive Only
12 m (40 ft.)
–
–
–
–
Drive with any Comm Option
12 m (40 ft.)
–
–
–
–
Drive with Remote I/O
12 m (40 ft.)
–
–
✔
–
E
Drive Only
30 m (98 ft.)
–
✔
–
–
Drive with any Comm Option
30 m (98 ft.)
–
✔
–
–
Drive with Remote I/O
30 m (98 ft.)
–
✔
✔
–
Fram
e
Second Environment
Restrict Motor Cable to 30 m (98 ft.)
First Environment Restricted Distribution
Restrict Motor Cable to 150 m (492 ft.)
Any Drive and Option
Any Drive and Option
External Filter Required
0-6 ✔
✔
✔