9.5 Serial Communication Configuration for DX83s
The DX83 Ethernet Bridge uses jumpers to select between RS-485 and RS-232 communications.
Install the four jumpers across the two top rows of pins for
RS-485 and across the bottom two rows of pins for RS-232.
Communication pins
9.6 Restoring Factory Default Settings
Restoring the factory default settings resets the settings for the IP address, the root login and root password, the HTTP
port setting, and a few other communication settings.
Restoring the factory default settings resets the settings for:
Parameter
Default Setting
IP Address
192.168.0.1
Root Login
root
Root Password
sxi
HTTP Port
80
Modbus Server Port
502
Telnet Port
23
EtherNet/IP Protocol
Disabled
Host Controller Systems
41