Operating Instructions

Latch Output Configuration: If the beam becomes blocked

while the System is running with Latch Output mode selected, 

the receiver outputs turn OFF within 24 ms. If the beam then 

becomes clear, the receiver Beam Status indicator will be Green 

and the Reset indicator will single-flash, indicating the System 

is waiting for a manual latch reset. In Latch Output mode, the 

outputs come back ON only when the beam is clear and after a

manual reset. The System will wait for a manual reset; when a 

valid reset signal is received and the beam remains clear, the 

receiver outputs turn ON. To perform a manual reset, close the 

Reset switch for 1/4 to 2 seconds, then open the switch. (For 

switch model MGA-KS0-1, described in Section 2, turn the key 

1/4 turn clockwise, hold for 1/4 to 2 seconds, then turn the key 

counterclockwise to its original position.)  
Internal Faults (Lockouts): If either sensor detects a critical

fault, scanning ceases, the receiver outputs turn OFF and 

diagnostic information is displayed through the sensor’s front

window. See Section 5 for resolution of error/fault conditions. 

4.5 Periodic Checkout Requirements

To ensure continued reliable operation, the System should be 

checked out periodically .
At every shift change, power-up and machine setup change, 

the Daily checkout should be performed; this checkout may be 

performed by a Designated or Qualified Person (see Section 6.4 

for the procedure). 
Semi-annually, the system and its interface to the guarded 

machine should be thoroughly checked out; this checkout must 

be performed by a Qualified Person (see Section 6.5). A copy of 

these test results should be posted on or near the machine .
Whenever changes are made to the System (either a new 

configuration of the EZ-SCREEN System or changes to the 

machine), the Commissioning Checkout should be performed 

(see Section 6.3).

4.4 Normal Operation

System Power-Up

The System will power up in one of two ways, depending on 

the Trip/Latch output configuration . If the System is set for Trip

output, it will power up and reset automatically; if the System is 

set for Latch output, it will require a manual reset procedure after 

power-up and sensor alignment.
Trip Output Mode Power-Up: When power is applied, each 

sensor will conduct self-tests to detect critical internal faults, 

determine configuration settings, and prepare the System for 

operation. (If either sensor detects a critical fault, scanning 

ceases, the receiver outputs remain OFF and diagnostic 

information is displayed through the sensor’s front window.) 

If no faults are detected, the System will automatically enter 

Alignment mode, with the receiver looking for an optical sync 

pattern from the emitter. If the receiver is aligned and receiving 

the proper sync pattern, it enters Run mode. No manual reset 

operation is required .
Latch Output Mode Power-Up: When power is applied, each 

sensor will conduct self-tests to detect critical internal faults, 

determine configuration settings, and prepare the System for 

operation. (If either sensor detects a critical fault, scanning 

ceases, the receiver outputs remain OFF and diagnostic 

information is displayed through the sensor’s front window.) 

If no faults are detected, the System will automatically enter 

Alignment mode, with the receiver looking for an optical sync 

pattern from the emitter. If the receiver is aligned and receiving 

the proper sync pattern, it begins scanning to determine the 

blocked or clear status of the beam. When the beam is aligned, 

the Yellow Reset indicator will double-flash to indicate the 

System is waiting for a manual reset. After a valid manual reset, 

the System enters Run mode .

During RUN Mode

Trip Output Configuration: If the beam becomes blocked

while the System is running with Trip output mode selected, the 

receiver outputs turn OFF within 24 ms (the maximum System 

response time). If the beam then becomes clear, the receiver 

outputs come back ON. No resets of any kind are needed. All 

required machine control resets are provided by the machine 

control circuit .