5.2.4 Salt Use Table
Notes:
1. Flow rates for refill controls are based on 60 psig (414 kPa) inlet pressure.
2. Take into account the type of brine system used when determining the actual amount of salt delivered during
regeneration. (i.e. dry salt/grid plate or wet salt)
3. Salt Use Table reflects minimum salting of 6 lbs./cu.ft. (96.11 kg/m
3
) through maximum salting of 15 lbs./cu.ft.
(240.27 kg/m
3
).
4. To use potassium chloride (KCl) increase salt dosage by approximately 25%.
5. Chloride/Anion dealkalizers regenerate with 5 lbs./cu.ft. (80.09 kg/m
3
) salt (NaCl) which yields approx. 7500 gr/
cu. ft. Injecting sodium hydroxide (NaOH) i.e. caustic soda, at a rate of 1/10 that of the salt dosage, during the
brine draw cycle, increases capacity to approx. 10000 gr./cu. ft. Exact capacity, based on tank size, must be
calculated using water analysis and resin manufacturer’s capacity curves.
Table 5.8 Model 942, 952, 952QC - Salt Used per Regeneration
Tank Size/Dia.
inches (cm)
14 (35.5)
16 (40.6)
18 (45.7)
21 (53.3)
24 ( 60.9)
30 (76.2)
36 (91.4)
Resin Volume
cu. ft. (cu. m.)
3 (0.85)
4 (0.113)
5 (0.142)
7 (0.200)
10
(0.283)
15
(0.425)
20
(0.566)
Refill Flow
Rate
GPM (LPM)
0.7 (2.65)
0.8 (3.03)
1.0 (3.78)
1.4 (5.30)
2.0 (7.57)
3.0
(11.36)
5.0
(18.93)
Salt Dial
Setting
(Minutes)
Approximate Pounds of Salt per Regeneration
8
18
--
--
--
--
--
120
10
21
24
30
42
60
90
150
12
25
29
36
50
72
108
180
14
29
34
42
59
84
126
210
16
34
38
48
67
96
144
240
18
38
43
54
76
108
162
270
20
42
48
60
84
120
180
300
22
45
53
66
92
132
198
--
24
--
60
75
105
150
225
--