Kenco Engineering SmartSonic Transmitter (Remote) User Manual

Page 36

Advertising
background image

Page 36

Defining the 4-20mA Error Signal (3.7mA or 22mA)

The

Pr 6 function allows you to define whether the following signal error indications Near Zone and Lost Echo will be

active when the current output reaches 22mA or 3.7mA. The SmartScan default setting enables 22mA analog current and
error messages to appear on its LCD display.

Near Zone - Whenever the level is below the defined Dead Zone

message will be displayed on the

SmartSonic Remote's LCD.

Lost Echo - whenever the level falls below the programmed 4mA value, or if the echo is lost,

message

will be displayed on the SmartSonic Remote's LCD.


Tank Empty – whenever the tank is empty or when the measured distance is higher than the tank height.

(typically in empty tanks with conic ending),

message will be displayed on the SmartSonic Remote's

LCD.



You can choose to enable or disable these error messages and 3.7mA/22mA analog signals as follows:

0: Enables 22mA signal error messages

1: Enables 3.7mA signal error messages

2: Disables signal error messages

Press / Action

Display

Description

Defining the 4-20mA Error Signal (3.7mA or
22mA) program

Displays the default value or the last entered
value.




and

Use to select between options 0, 1, or 2. Press
ENT to select

Advertising