Thermcraft XST-3-0-36-3V User Manual
Page 116
Configuration
Installation and Operation Handbook
6-18
2408 and 2404 Controller
Name
Description
Values Meaning
For ‘
id’ = ‘dC.OP’, ‘dc.rE’, or ‘dc.OP’ use this parameter table:
Func
Function
nonE Function disabled
HEAt Heating output
COOL Cooling output
PV
Retransmission of PV
wSP
Retransmission of setpoint
Err
Retransmission of error signal
OP
Retransmission of OP power
VAL.L
% PID, or Retrans’n Value,
giving minimum output
VAL.H
% PID, or Retrans’n Value,
giving maximum output
unit
voLt = Volts, mA = milliamps
Out.L
Minimum electrical output
Out.H
Maximum electrical output
For ‘
id’ = ‘LoG.i’ (i.e logic input) use the
LA Conf’ list on Page 6-13.
2A/b/C
Module 2 configuration
As per module 1 configuration, but excluding the ‘
SSr.1’, ‘SSr.2’ functions.
id
Identity of module installed.
As per module 2 plus:
tPSU
Transmitter power supply
Pot.i
Potentiometer input
For ‘
id’ = ‘Pot.i (i.e. potentiometer input module) use this parameter table:
Func
Function
nonE
Function disabled
rSP
Remote Setpoint
Fwd.i
Feedforward input
rOP.h
Remote OP power max.
rOP.L
Remote OP power min.
VPoS
Motorised valve position
VAL.L
Displayed value low
equivalent to 0%
potentiometer position
VAL.H
Displayed value high
equivalent to 100%
potentiometer position
VAL.L
Out.H
Out.L
VAL.H
Electrical
Output
%PID, or Retransmission Value
VAL.L
100%
0%
VAL.H
Displayed value
Potentiometer
position