Cal.s, None, User – Thermcraft XST-3-0-36-3V User Manual

Page 252

Advertising
background image

User Calibration

Installation and Operation Handbook

7-6

2416 Controller

Select Low-point Calibration
This is the Calibration Status display. This display shows that no
input is selected for calibration.
• nonE: No selection. If nonE selected go to page 7-4

• ip1.L: Input 1 (PV1) calibration low-point selected

• ip1.H: Input 1 (PV1) calibration high-point selected

• ip2.L:

Not available in Model 2416

• ip2.H:

Not available in Model 2416

Use

/

to select the parameter for the Low Calibration

point of Input 1, ‘

ip1.L’ & follow route shown on this page.

Press

Adjust low-point calibration

This is the display for adjusting the Low Calibration point of Input
1. The lower readout is a live reading of the process value, which
changes as the input changes.
Make sure that the calibration source is connected to the terminals
of Input 1, switched on and feeding a signal to the controller. It
should be set to the desired low-point calibration value. If the
lower readout does not show this value, then use

/

to adjust

the reading to the required value.

Press

to return to the ‘

ip-List’ header.


To perform the High-point Calibration, repeat the above
procedure, selecting ‘

ip1.H’ in the ‘CAL.S’ display for

adjustment.

Press

twice.

Calibration type

USEr’ was selected for the Low-point Calibration, and has

remained selected.

Press

CAL.S

nonE

CAL

USEr

Adj

25

x 2

Advertising
This manual is related to the following products: