Configuration
Installation and Operation Handbook
6-10
2416 Controller
The following parameters apply if the standard 8-segment programmer is to be configured.
PROG Programmer configuration Values
Meaning
PtyP Programmer type
nonE
Programmer disabled (
factory setting
)
1
8-segment programmer enabled
HbAc Holdback
SEG
ProG
Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.
Pwr.F Power fail recovery
cont
Continue from last setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
The following parameters apply if a 16-segment programmer is to be configured.
PROG Programmer configuration Values
Meaning
PtyP Programmer type
nonE
Programmer disabled
1
Single program
4
Four programs
HbAc Holdback
SEG
ProG
Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.
Pwr.F Power fail recovery
cont
Continue from last setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
out
Programmable event
outputs
no
YES
Disabled
Enabled
SYNC Synchronisation of programs
of several programmers
Not usable in Model 2416
no
YES
Disabled
Enabled
Select ‘
no’
Name
Description
Values
Meaning
HA
Comms 1 module config
id
Identity of the module
installed
cmS
EIA-232, or 2-wire EIA-485, or 4-wire
EIA-485 comms
PDS
PDSIO retransmission
PDS.i
PDSIO input