Table 2 — LID Display Data (cont)

EXAMPLE 9 — SERVICE2 DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT .

5. Scroll down to highlight SERVICE2.

6. Press SELECT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME DEFAULT VALUE

OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source

0,1

res

20 ma

0

DEMAND 20 mA Power Source

0,1

dem

20 ma

0

SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
CHWS Temp Enable

0-4

chws

en

0

CHWS Temp Alert

–40-245 (–40-118)

DEG F (DEG C) chws

al

245 (118)

CHWR Temp Enable

0-4

chwr

en

0

CHWR Temp Alert

–40-245 (–40-118)

DEG F (DEG C) chwr

al

245 (118)

Reset Temp Enable

0-4

rres

en

0

Reset Temp Alert

–40-245 (–40-118)

DEG F (DEG C) rres

al

245 (118)

Spare Temp 1 Enable

0-4

spr1

en

0

Spare Temp 1 Alert

–40-245 (–40-118)

DEG F (DEG C) spr1

al

245 (118)

Spare Temp 2 Enable

0-4

spr2

en

0

Spare Temp 2 Alert

–40-245 (–40-118)

DEG F (DEG C) spr2

al

245 (118)

Spare Temp 3 Enable

0-4

spr3

en

0

Spare Temp 3 Alert

–40-245 (–40-118)

DEG F (DEG C) spr3

al

245 (118)

OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source

0,1

sp1

20 ma

0

SPARE 2 20 mA Power Source

0,1

sp2

20 ma

0

SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
Spare Temp 4 Enable

0-4

spr4

en

0

Spare Temp 4 Alert

–40-245 (–40-118)

DEG F (DEG C) spr4

al

245 (118)

Spare Temp 5 Enable

0-4

spr5

en

0

Spare Temp 5 Alert

–40-245 (–40-118)

DEG F (DEG C) spr5

al

245 (118)

Spare Temp 6 Enable

0-4

spr6

en

0

Spare Temp 6 Alert

–40-245 (–40-118)

DEG F (DEG C) spr6

al

245 (118)

Spare Temp 7 Enable

0-4

spr7

en

0

Spare Temp 7 Alert

–40-245 (–40-118)

DEG F (DEG C) spr7

al

245 (118)

Spare Temp 8 Enable

0-4

spr8

en

0

Spare Temp 8 Alert

–40-245 (–0-118)

DEG F (DEG C) spr8

al

245 (118)

Spare Temp 9 Enable

0-4

spr9

en

0

Spare Temp 9 Alert

–40-245 (–40-118)

DEG F (DEG C) spr9

al

245 (118)

NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’ threshold for each point listed. If the ‘‘Enable’’
is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold
generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold
generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.

EXAMPLE 10 — SERVICE3 DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT .

5. Scroll down to highlight SERVICE3.

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Proportional Inc Band

2-10

gv

inc

6.5

Proportional Dec Band

2-10

gv

de

6.0

Proportional ECW Gain

1-3

gv

ecw

2.0

Guide Vane Travel Limit

30-100

%

gv

lim

50

29