background image

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

APPENDIX J – RECOMMENDED PERIODIC TESTING

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 179 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

APPENDIX J – RECOMMENDED PERIODIC TESTING

WARNING

Periodic testing of all boiler controls and safety devices is required to determine that they
are operating as designed. Precautions shall be taken while tests are being performed to
protect against bodily injury and property damage. The owner or user of an automatic boiler
system should set up a formal system of periodic preventive maintenance and testing.
Tests should be conducted on a regular basis and the results recorded in a log-book.

Table J1: Recommended Periodic Testing

Item

Frequency

Accomplished

By

Remarks

Refer to indicated sections of this manual for detailed procedures

Gauges, monitors and
indicators

Daily

Operator

Visual inspection and record readings in
operator log

Instrument and
equipment settings

Daily

Operator

Visual check against factory recommended
specifications

Weekly

Operator

Verify factory settings

Firing Rate Control

Semi-

Annually

Service

Technician

Verify factory settings

Annually

Service

Technician

Check with combustion calibration test
equipment. See section 7.4 and Chapter 4.

Flue, vent, stack or
intake air duct

Monthly

Operator

Visually inspection condition and check for
obstructions

Spark Igniter-Injector

Weekly

Operator

See section 7.2

Air/Fuel Valve position

Weekly

Operator

Check position indicator dial (section 3.11)

SSOV Leakage test

Annually

Service

Technician

Check for leakage in accordance with the
SSOV manufacturer’s (Siemens)
recommendations.

Flame failure

Weekly

Operator

Close manual gas shutoff valve and check
safety shutdown. See section 6.7

Flame signal strength

Weekly

Operator

Check flame strength using the Control
Panel Operating Menu. See section 3.4.

Low water level cut off
and alarm

Weekly

Operator

See section 6.4

Slow drain test

Semi-

Annually

Operator

Perform a slow drain test in accordance with
ASME Boiler and Pressure Vessel Code,
Section IV.

High water
temperature safety
control test

Annually

Service

Technician

See section 6.5

Operating controls

Annually

Operator

See section 3.2