AERCO BMK 1000 User Manual

Page 39

Advertising
background image

Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0082_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 39 of 192

GF-130

Ph.: 800-526-0288

05/21/2014

Table 3-1: Operating Controls, Indicators and Displays

ITEM

FEATURE

FUNCTION

1

LED Status Indicators

Four (4) Status LEDs indicate the current operating status as follows:

COMM

Lights when RS-232 communication is occurring

MANUAL

Lights when the valve position (fire rate) is being controlled
using the front panel keypad. This mode of operation is for
service technician use only.

REMOTE

Lights when the unit is being controlled by an external signal
from an Energy Management System

DEMAND

Lights when there is a demand for heat.

2

OUTLET
TEMPERATURE

Display

3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the display
lights to indicate whether the displayed temperature is in
degrees Fahrenheit or degrees Celsius. The °F or °C blinks
when operating in the Deadband Mode.
On a BST Master, display flashes & shows header temperature.

3

VFD Display

Vacuum Fluorescent Display (VFD) consists of 2 lines each
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:
• Startup Messages
• Fault Messages
• Operating Status Messages
• Menu Selection
• BST Messages

4

RS-232 Port

Port permits a Laptop Computer or External Modem to be
connected to the unit’s Control Panel. AERCO offers for
purchase the RS232 Adaptor Cable (P/N 124675), which is
designed to work with this port. This cable features a DB9
connector for connection to older computers with serial ports or
can be used with a Serial-to-USB adaptor for use in modern
computer USB ports.

5

FAULT Indicator

Red FAULT LED indicator lights when a boiler alarm condition
occurs. An alarm message will appear in the VFD.

6

CLEAR Key

Turns off the FAULT indicator and clears the alarm message if
the alarm is no longer valid. Lockout type alarms will be latched
and cannot be cleared by simply pressing this key.
Troubleshooting may be required to clear these types of alarms.

7

READY Indicator

Lights ON/OFF switch is set to ON and all Pre-Purge conditions
have been satisfied.

8

ON/OFF Switch

Enables and disables boiler operation.

9

LOW WATER LEVEL
TEST/RESET

Switches

Allows operator to test operation of the water level monitor.
Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Pressing the CLEAR key (item 6) resets the display.

Advertising
This manual is related to the following products: