1 remote interlock in, 2 delayed interlock in, 10 fault relay – AERCO KC1000 Low NOx Boiler July 2011 User Manual

Page 20: 8 auxiliary relay contacts, Installation

Advertising
background image

INSTALLATION

2-10

NOTE:

Both the Delayed Interlock and Remote

Interlock must be in the closed position to

allow the unit to fire.

2.7.9.1 REMOTE INTERLOCK IN

The remote interlock circuit (REMOTE INTL’K

IN) is provided to remotely start (enable) and

stop (disable) the Boiler if desired. The circuit is

24 VAC and comes factory pre-wired closed

(jumpered).

2.7.9.2 DELAYED INTERLOCK IN

The delayed interlock circuit (DELAYED INTL’K

IN) is typically used in conjunction with the

auxiliary relay described in paragraph 2.8. This

interlock circuit is located in the purge section of

the start string. It can be connected to the

proving device (end switch, flow switch etc.) of

an auxiliary piece of equipment started by the

boiler’s auxiliary relay. The delayed interlock

must be closed for the boiler to fire. If the

delayed interlock is connected to a proving

device that requires time to close (make), a time

delay (Aux Start On Dly) that holds the start

sequence of the boiler long enough for for a

proving switch to make can be programmed.

Should the proving switch not prove within the

programmed time frame, the boiler will shut

down. The Aux Start On Dly can be

programmed from 0 to 120 seconds. This option

is locate in the Configuration Menu (Section 3).

2.7.10 FAULT RELAY

The fault relay is a single pole double throw

(SPDT) relay having a normally open and

normally close set of relay contacts that are

rated for 5 amps at 120 VAC and 5 amps at 30

VDC. The relay energizes when any fault con-

dition occurs and remains energized until the

fault is cleared and the CLEAR button is

depressed. The fault relay connections are

shown in Figure 2.11.

2.8 AUXILIARY RELAY CONTACTS

Each KC Boiler is equipped with a single pole

double throw (SPDT) relay that is energized

when there is a demand for heat and de-

energized after the demand for heat is satisfied.

The relay is provided for the control of auxiliary

equipment, such as pumps and louvers, or can

be used as a Boiler status indictor (firing or not

firing). Its contacts are rated for 120 VAC @ 5

amps. Refer to Figure 2.11 to locate the AUX

RELAY terminals for wiring connections.

2.9 FLUE GAS VENT INSTALLATION

The AERCO Venting and Combustion Air Guide,

GF-1050, must be consulted before any flue or

inlet air venting is designed or installed.

Suitable, U/L approved, positive pressure,

water-tight vent materials as specified in

AERCO’s GF-1050, must be used for safety and

UL certification. Because the unit is capable of

discharging low temperature exhaust gases, the

flue must be pitched back to the unit a minimum

of 1/4" per foot to avoid any condensate pooling

and to allow for proper drainage.

While there is a positive flue pressure during

operation, the combined pressure drop of vent

and combustion air systems must not exceed

140 equivalent feet of 0.81” W.C. Fittings as well

as pipe lengths must be calculated as part of the

equivalent length. For a natural draft installation

the draft must not exceed - 0.25” W.C. These

factors must be planned into the vent

installation. If the maximum allowable equivalent

lengths of piping are exceeded, the unit will not

operate properly or reliably.

For Massachusetts boiler installations, the

Heatfab Division of the Selkirk Corporation

provides vent systems which conform to all

applicable requirements for installations within

the Commonwealth of Massachusetts. Contact

information for this supplier is as follows:

Selkirk Corporation

Heatfab Division

130 Industrial Blvd.

Turners Falls, MA 01376

Phone: 1-800-772-0739

www.heat-fab.com

2.10 COMBUSTION AIR

The AERCO Venting and Combustion Air Guide,

GF-1050, MUST be consulted before any flue or

combustion supply air venting is designed or

started. Combustion air supply is a direct

requirement of ANSI 223.1, NFPA-54, CSA

B149.1 and local codes. These codes should be

consulted before a permanent design is

determined.

The combustion air must be free of chlorine,

halogenated hydrocarbons, or other chemicals

that can become hazardous when used in gas-

fired equipment. Common sources of these

compounds are swimming pools, degreasing

compounds, plastic processing and refrigerants.

Whenever the environment contains these types

of chemicals, combustion air must be supplied

Advertising