Figure 7.1, Spark igniter and flame detector location, Maintenance – AERCO KC1000 Low NOx Boiler July 2011 User Manual

Page 55: Warning

Advertising
background image

MAINTENANCE

7-1

SECTION 7 - MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to

keep up efficiency and reliability. For best

operation and life of the unit, the routine

maintenance procedures listed in Table 1 should

be performed within the specified time periods.

Appendix K contains recommended spare parts

lists for maintenance of the KC1000 Boiler.

Table 1 Maintenance Schedule

Para

Item

6

Mos.

12

Mos.

24

Mos.

Labor

Time

7.2

Spark

Igniter

(124570)

Inspect Replace

20

mins.

7.3

Flame

Detector

(G124837)

Inspect Replace

20

mins.

7.4 Combustion

Cal.

Check Check

1 hr.

7.5 Testing of

Safety

Devices

Test

20

mins.

7.6 *Manifold &

Tubes

Inspect

& clean

if

needed

4 hrs.

7.7 Water Side

Inspection

Inspect 2 hr.

7.8 Condensate

Drain

Inspect

& clean

30

mins.

* Recommended only when unit will be run in an

extreme condensing mode for prolonged periods

of time.

WARNING!

TO AVOID PERSONAL INJURY, BEFORE

SERVICING:

(A) DISCONNECT AC POWER FROM THE

UNIT.

(B) SHUT OFF THE GAS SUPPLY TO THE

UNIT.

(C) ALLOW THE UNIT TO COOL TO A SAFE

TEMPERATURE.

7.2 SPARK IGNITER

The spark igniter assembly (124570) is located

in the body of the burner (Figure 7.1). The igniter

may be HOT. Care should be exercised. It is

easier to remove the igniter from the unit after

the unit has cooled to room temperature.

To inspect or replace the Igniter (124570):

1. Set the

ON/OFF switch on the control panel

to the

OFF position and disconnect AC

power from the unit.

2. To access the spark igniter, remove the

unit’s left side paneland left rear cover.

3. Disconnect the igniter cable from the igniter

contact.

4. Using a 15/16” open-end wrench, remove

the igniter from the burner shell.

5. Inspect the igniter for erosion or carbon

build-up. If there is substantial erosion of the

spark gap or ground electrode, the igniter

should be replaced. If carbon build-up is

present, clean the igniter using fine emery

cloth. Repeated carbon build-up on the

igniter is an indication that a check of the

combustion settings is required. See

Section 4 for Combustion Calibration

procedures.

6. Prior to reinstalling the igniter, a conductive

anti-seize compound must be applied to the

igniter threads.

7. Reinstall the igniter in the burner shell. Do

Not over-tighten. A slight snugging up is

sufficient.

8. Reconnect the igniter cable.

9. Replace the left side panel and left rear

cover on the unit.

FLAME

DETECTOR

PROBE

LOWER

BURNER

SHELL

BURNER

HEAD

BURNER

PLATE

IGNITER

(124570)

FLAME DETECTOR

(124837)

STAGED

IGNITION

ORIFICE


Figure 7.1

Spark Igniter and Flame Detector Location

Advertising