INITIAL START-UP

4-8

22. Wait for the analyzer to settle and then

compare the new oxygen reading to Table 6

(or 6A). Repeat the inlet air shutter

adjustment until the oxygen is within the

specified range. Also, ensure that the CO

and NOx emissions do not exceed the

values shown. Firmly tighten the inlet air

shutter locking nuts when finished.

REMINDER:

At 30% valve position, adjust only the differential

pressure regulator. At 100% valve position,

adjust only the inlet air shutter.

23. If the measured oxygen reading is above the

oxygen range in Table 6 (or 6A), loosen the

two 7/16" locking nuts securing the inlet air

shutter. Close the air shutter 1/4” to 1/2” to

decrease the oxygen level and tighten the

two nuts.

24. Allow the analyzer to settle then compare

the new oxygen reading to Table 6 (or 6A).

25. Repeat the adjustment until the oxygen is

within the specified range. Also, ensure that

the CO and NOx readings do not exceed the

values shown. Firmly tighten the inlet air

shutter locking nuts when finished.

NOTE:

Adjust the inlet air shutter only at 100% valve

position. Do Not adjust the differential pressure

regulator.

26. Change the valve position to 30%. Allow

time for the combustion analyzer to settle.

Check the measured oxygen level, CO and

NOx emissions to ensure that they are still

within the ranges shown in Table 4.

27. Continue these procedures until all oxygen

levels are within the ranges specified in

Tables 4, 5 and 6 (or 6A).

28. Record all readings on the AERCO start-up

sheet provided with each unit. Proceed to

paragraph 4.5 when all propane combustion

calibration procedures are completed.

4.5 UNIT REASSEMBLY

Once combustion calibration is set properly, the

unit can be re-assembled for permanent

operation.

1. Set the

ON/OFF switch to the OFF position.

Disconnect the AC power supply from the

unit.

2. Shut off the gas supply to the unit.

3. Remove the differential pressure regulator

cap and cap gasket (see Figure 4.3).

4. Apply a drop of silicone adhesive to the

regulator adjusting screw to lock its setting.

5. Reinstall the cap and gasket on the

regulator. Tighten the cap using a

screwdriver or wrench.

6. Remove all of the manometers and barbed

fittings and reinstall the pipe plugs using a

suitable thread compound.

7. Remove the combustion analyzer probe

from the vent hole. Seal the probe hole and

replace the vent connection cover.

8. Replace the unit’s panels and hood.

4.6 OVER TEMPERATURE LIMIT

SWITCH ADJUSTMENTS

There are two Over-Temperature Limit switches

that turn off the unit when the outlet water

temperature becomes too hot. The lower over-

temperature limit switch is adjustable and should

be adjusted 20°F to 40°F above the operating

header temperature. The upper over-

temperature limit switch is a manual reset device

and is not adjustable. It will shut the unit off if the

water temperature reaches 240°F.

DO NOT

attempt to adjust its setpoint.

To adjust the lower over temperature switch limit

switch, proceed as follows:

1. Remove the wing nut from the top center of

the shell cap. Lift the cap off the shell.

2. The two over-temperature limit switches are

located at the top of the shell (Figure 4.5).

DO NOT

adjust the upper switch which has

been factory preset. Adjust the lower switch

between 20°F to 40°F higher than the

maximum header temperature the unit may

reach.

3. Replace the shell cap and wing nut.