SilentKnight 5820XL User Manual

Page 127

Advertising
background image

Model 5820XL / 5820XL-EVS Installation Manual

LS10061-001SK-E

7-19

Table 7-6: Menu choices for Internal/External Power Module

Choices

Type Selections

Function

Selections for

each Type

Comments

Enter Point

Select Type

UNUSED

B NOTIF

NOTIF OUT

CTRL CKT

A NOTIF

AUX PWR

CONSTANT

Constant auxiliary power.

RESETTABLE

Resettable auxiliary power.

DOOR

Door holder auxiliary power.

SOUNDER SYNC

Sounder Sync auxiliary Power

B SWITCH

MANUAL PULL

Refer to comments column of
Table 7-5 for description of these options.

Latch or Non-latching feature only appears for
waterflow, supervisory, tamper, zone aux1, zone
aux2, system aux1, and system aux2.

WATERFLOW

FIRE SUPERVISORY

TAMPER

FIREDRILL

SILENCE

RESET

PAS_ACK

ZONE AUX1

ZONE AUX2

SYSTEM AUX1

SYSTEM AUX2

MANUAL RELEASE

INTERLOCK

STATUS POINT

Non-latching - Used to activate an ancillary Output
Group that does not active alarm, sound PZT,
display status or report events. Reset has no affect
on this point

A SWITCH

Same as B SWITCH

B DETECT

2-WIRE SMK

Used for Class B, 2-wire detectors.

4-WIRE SMK

Used for Class B, 4-wire detectors.

4-WIRE CO SMK

Used for Class B, 4-wire CO detectors

A DETECT

2-WIRE SMK

Used for Class A, 2-wire detectors.

4-WIRE SMK

Used for Class A, 4-wire detectors.

4-WIRE CO SMK

Used for Class A, 4-wire CO detectors.

Select Zone/Group

Group or Zone selection will appear depending on
the type selected.

Edit Name

See Section 7.5.5.

Advertising