Table 7-6: Menu choices for Internal/External Power Module
Choices
Type Selections
Function
Selections for
each Type
Comments
Enter Point
Select Type
UNUSED
B NOTIF
NOTIF OUT
CTRL CKT
A NOTIF
AUX PWR
CONSTANT
Constant auxiliary power.
RESETTABLE
Resettable auxiliary power.
DOOR
Door holder auxiliary power.
SOUNDER SYNC
Sounder Sync auxiliary Power
B SWITCH
MANUAL PULL
Refer to comments column of
Table 7-5 for description of these options.
Latch or Non-latching feature only appears for
waterflow, supervisory, tamper, zone aux1, zone
aux2, system aux1, and system aux2.
WATERFLOW
FIRE SUPERVISORY
TAMPER
FIREDRILL
SILENCE
RESET
PAS_ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
Non-latching - Used to activate an ancillary Output
Group that does not active alarm, sound PZT,
display status or report events. Reset has no affect
on this point
A SWITCH
Same as B SWITCH
B DETECT
2-WIRE SMK
Used for Class B, 2-wire detectors.
4-WIRE SMK
Used for Class B, 4-wire detectors.
4-WIRE CO SMK
Used for Class B, 4-wire CO detectors
A DETECT
2-WIRE SMK
Used for Class A, 2-wire detectors.
4-WIRE SMK
Used for Class A, 4-wire detectors.
4-WIRE CO SMK
Used for Class A, 4-wire CO detectors.
Select Zone/Group
Group or Zone selection will appear depending on
the type selected.
Edit Name