4 wiring specifications, Wiring specifications – SilentKnight 5820XL User Manual
Page 22
Model 5820XL / 5820XL-EVS Installation Manual
LS10061-001SK-E
3-3
3.4
Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone
communication or cause false alarms. To avoid induced noise, follow these guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for
the entire panel. Instead, separate the wiring as follows:
•
Do not pull wires from different groups through the same conduit. If you must run them together, do so for
as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You
must route high and low voltages separately.
•
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it
could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed
circuits. See Figure 3-1 for an example.
•
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be
reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
35
SC-
L2
SLC IN
Used for Class A installations
0
36
SC+
37
Ring
Phone Line 1 Telco Ring
N/A
0
38
Tip
Phone Line 1 Telco Tip
39
Ring
Phone Line 1 Premises Ring
40
Tip
Phone Line 1 Premises Tip
41
Ring
Phone Line 2 Telco Ring
N/A
0
42
Tip
Phone Line 2 Telco Tip
43
Ring
Phone Line 2 Premises Ring
44
Tip
Phone Line 2 Premises Tip
45
SC-
SLC Programming Terminal
(-)
32 VDC
150 mA
0
46
SC+
SLC Programming Terminal
(+)
32 VDC
150 mA
High voltage
AC power, Terminals 1-3
SLC loops
Terminals 33-36
Audio input/output
Phone line circuits, Terminals
37-44
Notification circuits
Terminals 4-15
SBUS Terminals
16-23
Relay circuits
Terminals 24-32
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal # and Label
Description
Rating
Earth Ground
Faults
Voltage
Current