SilentKnight 5820XL User Manual
Page 27
LS10061-001SK-E
Before You Begin Installation
3-8
SLC Modules
B200SR Sounder Base
(99 max/loop
& 396 max/
panel)
Aux Pwr
Standby: .50 mA
mA
Alarm: 35 mA
mA
SLC
Standby .30 mA
mA
B200S Sounder Base
Aux
Standby .50 mA
mA
Alarm (high vol) 35 mA
mA
SLC
Standby .30 mA
mA
B200SR-LF Low Frequency
Sounder Base
Aux Pwr
Standby: 1 mA
mA
Alarm: 125 mA
mA
B200S-LF Low Frequency Sounder
Base
Aux
Standby .55 mA
mA
Alarm (high vol) 140 mA
mA
SLC
Standby .30 mA
mA
B224RB Relay Base
Standby/Alarm: 0.5 mA
mA
mA
RTS151/151 KEY
Alarm: 7.5 mA
mA
RA100Z
Alarm: 10 mA
mA
SLC Isolator Devices
SK-ISO (Isolator Module)
(100 max/loop
& max/panel)
Standby/Alarm: .45 mA
mA
mA
ISO-6 (6 Fault Isolator Module)
Standby: (per circuit) .45 mA
mA
Alarm: (per circuit) 17 mA
mA
B224BI Isolator Base
Standby/Alarm: .5 mA
mA
mA
Accessories Modules
5815XL SLC Expander
(3 max.)
Standby/Alarm: 55 mA
mA
mA
5860 Remote Fire Alarm
Annunciator
* EVS-RCU contains one 5860 and
must be added to the calculation
here.
(12 max.)
Standby: 20 mA
mA
Alarm: 25 mA
mA
5824 Serial/Parallel Printer
Interface Module
(2 max.)
Standby/Alarm: 45 mA
mA
mA
5496 Intelligent Power Module
(8 max.)
Standby/Alarm: 10 mA
mA
mA
5895XL IntelliKnight Power Module
Standby/Alarm: 10 mA
mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 I/O Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
EVS-VCM Voice Control Module
(1 max.)
Standby: 70 mA
mA
Alarm: 100 mA
mA
EVS-SW24 Switch Expander
(5 max.)
Standby: 10 mA
mA
Alarm: 25 mA
mA
EVS-50W or EVS-125W Audio
Amplifier with/without EVS-CE4
(4 max.)
Standby: 10 mA
mA
Alarm: 10 mA
mA
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current