Delta Electronics Pulse Generator Card EME-PG01 User Manual

Eme-pg01, Layout, Installation

Advertising
background image

2007-07-09

5011659701-TPG1

EME-PG01

Pulse Generator Card for VFD-E Series Instruction Sheet

Please thoroughly read this instruction sheet before installing option cards and putting them into use.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the

most updated version at http://www.delta.com.tw/industrialautomation.

X

Layout

PG Card (EME-PG01)

Pul se Fe ed ba ck

Pulse Outp ut

Y

Installation

Make sure that the AC Motor Drive is powered off before operation.
DO NOT insert or remove the card when the AC Motor Drive is
powered on.

Please mount the extension card as shown and fix it with the screw
packed with the card.

Screw torque:
Maximum 2kgf-cm

Terminals Screw Torque: Maximum 2kgf-cm

Wire Length

Types of Encoder Output

Maximum Length

Wire

Gauge

Voltage

50m

Open Collector

50m

Line Driver

300m

Complementary

70m

14 ~ 24 AWG

(2.1 ~ 0.2 mm

2

)

NOTE

EME-PG01 needs additional power source DC 5 ~ 24V, as to
details please refer to table of terminals descriptions.

Only when the extension card is correctly installed on the AC
Motor Drive, the extension card will be automatically detected.
The parameters can be set in Group 13. If extension card is not
installed, only parameters Group 0 ~ Group 10 can be set.
Refer to Chapter 5: Parameters in the user manual for further
details.

Z

Notes

Please use a shielded cable to prevent interference. Do not run
control wires parallel to any high voltage AC power line (200 V and
above).

The wire length and signal frequency are in inverse proportion.

Always use this product in a clean indoor location free from dust,
corrosive gas and liquid.

When the relays are used to switch inductive loads (relays,
contactors, motors, etc), connect an RC network or Varistor parallel
to the load to suppress voltage spikes.

For safety, it is recommended to use fuses for the circuitry that is
switched by the relays. The fuse specification must be within the
specified contact limits.

The ends of wires must be tinned or crimped.

To avoid interference, route the extension card wires separately and
as far away (at least 15cm) as possible from other control wires,
motor wires and power wires, etc. Where these wires must cross
each other, please make sure they are at a 90

o

angle.

Always use and operate this product within the limit of its
specifications.

[

Specification

Environmental

Operating Temperature

-10

o

C to 50

o

C (non-condensing and not frozen)

Storage Temperature

-20

o

C to + 60

o

C

Ambient Humidity

Less than 90%RH (non-condensing)

Installation Altitude

Below 1000m

Vibration

Below 20 Hz: Maximum 9.81 m/s

2

(1G);

20 ~ 50Hz: Maximum 5.88 m/s

2

(0.6G)

Terminals Descriptions

Terminal Symbols

Descriptions

Vcc

Input Voltage: DC 5 ~ 24V
When the encoder output type is voltage output,
input voltage is DC 12 ~ 24V

0V

Power source and input signal common

A ,

B ,

A

B

Input signal from the encoder. Input type is selected
by SW2. It can be 1-phase or 2-phase input.
Maximum 300KP/sec

A/O, B/O

Output signal from the encoder.
Open collector: max. output DC24V 50mA

Grounding

\

Types of Encoder Output

Types of Encoder

Output

SW2

Wiring Diagram

Voltage

O/P

0V

VCC

OC

TP

Line driver

Q

Q

OC

TP

Complementary

O/P

0V

VCC

OC

TP

R(L1)

S(L2)

T(L3)

NFB

R

S

T

U(T1)

V(T2)

W(T3)

Motor

3~

VFD-E

OC

TP

A

B

Vcc

0V

A

B

A/O
B/O

RPM Meter

*The power source of RPM meter

is supplied by the customers.

0V

A

B

A

B PG

EME-PG01

DC

5~24V

+

-

GND

Vin

O/P

0V

VCC

OC

TP

R(L1)

S(L2)

T(L3)

NFB

R

S

T

U(T1)

V(T2)

W(T3)

Motor

3~

VFD-E

OC

TP

A

B

Vcc

0V

A/O
B/O

RPM Meter

*The power source of RPM meter

is supplied by the customers.

0V

A

B

A

B

PG

EME-PG01

DC

5~24V

+

-

GND

Vin

Open

collector

Note: Based on the design, the input signal terminals from

the encoder should be connected to the terminals
of

A

and

B

on EME-PG01 card, not the terminals of

A and B, so as to avoid damage to the encoder.