Delta Electronics Analog Output Module DVP02DA-S User Manual

Fg v+ i+ com c h 1 fg v+ i+ com c h 2, Warning, Introduction

Advertising
background image

Warning

Please carefully read this instruction thoroughly prior to use the DVP02DA-S.
The DC input power must be OFF before any maintenance.
This is an OPEN-TYPE built-in DVP02DA-S, and the DVP02DA-S is certified to meet the safety requirements of

IEC 61131-2 (UL 508) when installed in the enclosure to prevent high temperature, high humidity, exceessive
vibration, corrosive gases, liquids, airbome dust or metallic particles. Also, it is equipped with protective methods
such as some special tool or key to open the enclosure, so as to avoid the hazard to users or any damage to the
DVP02DA-S.

DO NOT connect the AC power to any of the input/output terminals, or it may the DVP02DA-S. Make sure that all

the wiring is well conducted prior to power on.

DO NOT touch the internal circuit for at least 1 minute after the power is OFF.

Make sure that DVP02DA-S is properly grounded

, to avoid any electromagnetic noise.

Introduction

Model Explanation & Peripherals

Thank you for choosing Delta DVP PLC Series. The analog output module of DVP02DA-S series can

read/write the data of analog output module by using instructions FROM/TO via DVP-PLC

SS/SA/SX/SC/SV Series MPU program. The analog output module receives 2 group 12-bit digital data

from PLC MPU and converts it into 2 points analog output signal (voltage or current). There are 49 CR

(Control Register) in each module and there are 16 bits in each register.

The software version of DVP02DA-S analog output module can be updated via RS-485 communication.

Power unit and module are separate. Size is small and easy to install.

Users can select output either voltage or current via wiring. Voltage output range is 0V ~ +10V DC

(resolution is 2.5mV). Current output range is 0mA ~ 20mA (resolution is 5µA).

Product Profile & Outline

90.00

4.00

3.00

25.20

1

2

3

4

60.00

5

6

7

8

9

3

10

FG

V+

I+

COM

C
H
1

FG

V+

I+

COM

C
H

2

11

12

13

3.4

90.00

60.00

3.00

14

Unit:mm

1. Status indicator (POWER, RUN and ERROR)

8. Extension port

2. Model name

9. Extension unit clip

3. DIN rail clip

10. DIN rail (35mm)

4. I/O terminals

11. RS-485 communication port

5. I/O point indicator

12. Mounting rail for extension unit

6. Mounting hole of the extension unit

13. DC power input

7. Nameplate

14. Extension port

ENGLISH

External Wiring

Voltage output
0V ~ 10V

V+

* 2

 

FG

COM

V+

FG

I+

CH1

CH2

24+

24-

AG

+15V

-15V

DC/DC

converter

* 3

 

System
Grounding

Class 3 Grounding

(100 or less)

Ω

DC24V

I+

Current output

0mA~20mA

COM

CH1

CH2

Isolation wire 1

 

Isolation wire 1

 

AC drive, recorder,
scale valve...

AC drive, recorder,
scale valve...

terminal of
power module

DVP02DA-S

V+

I+

COM

FG
V+

I+

COM

FG

Note 1: Please isolate analog output and other power wiring.
Note 2: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1 ~ 0.47
µF

25V for noise filtering.

Note 3: Please connect

power module terminal and

analog output module terminal to system earth point and

make system earth point be grounded or connects to machine cover.

Warning: DO NOT wire to the No function terminal

Specifications

Functions

Digital/Analog (2D/A) module

Voltage output

Current output

Power supply voltage

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)

Analog input channel

2 channels/each module

Analog output range

0 ~ 10V

0 ~ 20mA

Digital data range

0 ~ 4,000

0 ~ 4,000

Resolution

12 bits (1

LSB

=2.5mV)

12 bits (1

LSB

=5µA)

Output impedance

0.5Ω or lower

Overall accuracy

±0.5% of full scale of 25°C (77°F).
±1% of full scale during 0 ~ 55°C (32 ~ 131°F).

Response time

3ms × channels

Max. output current

20mA (1KΩ ~ 2MΩ)

Tolerance carried
impedance

0 ~ 500Ω

Digital data format

2’s complementary of 16-bit, 13 significant bits.

Isolation method

Isolation between digital area and analog area. But no isolation among
channels.

Protection

Voltage output has short circuit protection but a long period of short circuit
may cause internal wire damage and current output break.

Communication mode
(RS-485)

Modbus ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/
38,400/ 57,600/115,200. For ASCII mode, format is 7 bits, even, 1 stop bit (7,
E, 1), while RTU mode format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is
disabled when the DVP02AD-S is connected in series with an MPU.

Connect to DVP-PLC MPU
in series

If DVP02DA-S modules are connected to MPU, the modules are numbered
from 0 - 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the
max and they DO NOT occupy any digital I/O points of the MPU.

Other Specifications

Power supply

Max. rated power
consumption

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 3W, supply from external
power.

Environment

Operation/storage

1. Operation: 0°C~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2
2. Storage: -25°C~ 70°C (temperature), 5 ~ 95% (humidity)

Vibration/shock immunity

Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

CR (Control Register)

CR

#

RS-485

parameters

address

Latched

Register name

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#0

H’4032

○ R Model type

System used, data length is 8 bits (b7 ~ b0).
DVP-04AD model code=H’49.

User can read the data from program to check if there is
extension module.

Reserved

CH2

CH1

#1

H’4033

○ R/W Output mode setting

Output mode setting: default setting is H’0000.

Mode 0: output voltage mode (0V ~ 10V).
Mode 1: output voltage mode (2V ~ 10V).

Mode 2: output current mode (4mA ~ 20mA).
Mode 3: output current mode (0mA ~ 20mA).

Mode 4: none use.

CR#1: CR#1 is used to set two internal channels working mode of analog output module. Every channel has four
modes to set that can set individually. For example: if set CH1 to mode 2 (b2 ~ b0 = 010), CH2 to mode 1 (b5 ~ b3 =
001). It needs to set CR#1 to H’000A.

#10

H’403C

╳ R/W CH1 output value

#11

H’403D

╳ R/W CH2 output value

The output setting range of channel CH1 ~ CH2 is K0 ~
K4,000. Default setting is K0 and unit is LSB.

#22

H’4048

○ R/W To adjust OFFSET value of

CH1

#23

H’4049

○ R/W To adjust OFFSET value of

CH2

It is used to set the OFFSET value of CH1 ~ CH2.
The setting range is K-2,000 ~ K2,000.
The default setting is K0 and unit is LSB.

#28

H’404E

○ R/W To adjust GAIN value of CH1

#29

H’404F

○ R/W To adjust GAIN value of CH2

It is used to set the GAIN value of CH ~ CH2.
The setting range is K0 ~ K4,000.

The default setting is K2,000 and unit is LSB.

CR#22~CR#29: Please be noticed that GAIN value – OFFSET value=+400

LSB

~+6,000

LSB

(voltage or current).

When this value within this range, the resolution of the output signal will be thin and the value variation will be larger.
When this value exceeds this range, the resolution of output signal will be thick and the variation of value will be
smaller.

CR

#

RS-485

parameters

address

Latched

Register name

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#30

H’4050

╳ R Error status

It is the data register to save all error status.
Please refer to error code chart for detail.

CR#30 is the error code. Please refer to the following chart.

Error description

Content

b15 ~ b8

b7

b6

b5

b4

b3

b2

b1

b0

Power source abnormal

K1 (H’1)

0

0

0

0

0

0

0

1

Analog input value error

K2 (H’2)

0

0

0

0

0

0

1

0

Setting mode error

K4 (H’4)

0

0

0

0

0

1

0

0

Offset/gain error

K8 (H’8)

0

0

0

0

1

0

0

0

Hardware malfunction

K16 (H’10)

0

0

0

1

0

0

0

0

Digital range error

K32 (H’20)

0

0

1

0

0

0

0

0

Average times setting error K64 (H’40)

0

1

0

0

0

0

0

0

Instruction error

K128 (H’80)

Reserved

1

0

0

0

0

0

0

0

Note: Each error code will have corresponding bit (b0 ~ b7). Two or more errors may happen at the same time. 0 means

normal and 1 means error happened.

EX: if the digital input exceeds 4,000, error (K2) will occur. If the analog output exceeds 10V, both analog input value

error K2 and K32 will occur.

#31

H’4051

○ R/W Communication address

setting

It is used to set RS-485 communication address. The
setting range is from 1 to 254 and the default setting is K1.

#32

H’4052

○ R/W

Communication baud rate
setting

It is used to set communication baud rate (4,800/9,600/
19,200/38,400/57,600/115,200 bps).
Communication format: ASCII mode is 7 bits, even bit, 1
stop bit (7, E, 1), while RTU mode is 8 bits, even bit, 1 stop
bit (8, E, 1).
b0: 4,800 bps (bit/sec).
b1: 9,600 bps (bit/sec) (default setting).
b2: 19,200 bps (bit/sec).
b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec).
b5: 115,200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code
(only for RTU mode).
b15: ASCII/RTU mode selection.

Reserved

CH2

CH1

#33

H’4053

○ R/W

Reset to default setting and
set characteristics adjustable
priority

Output latched setting, default setting H’0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of

CH1 (CR#22, CR#28). When b1=1, inhibit user to
adjust OFFSET and GAIN value of CH1 (CR#22,
CR#28).

2. b1 means if characteristic register is latched. b1=0

(default setting, latched), b1=1 (not latched).

3. When b2 is set to 1, all settings will be reset to default

setting.

CR#33 is used to set the internal function priority. For example: characteristic register. Output latched function will
save output setting to the internal memory before power loss.

#34

H’4054

○ R Software version.

In hexadecimal to display software version.
For example: H’010A means 1.0A.

#35 ~ #48

System used

Symbols:

○ means latched.

╳ means not latched.
R means can read data by using FROM instruction via RS-485.

W means can write data by using TO instruction via RS-485.

LSB (Least Significant Bit): 1. Voltage output: 1

LSB

=10V/8,000=2.5mV.

2. Current output: 1

LSB

=20mA/4,000=5µA.

※ The corresponding parameters address H’4032 ~ H’4054 of CR#0 ~ CR#34 are provided for user to read/

write data via RS-485.
A. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
B. Communication format: ASCII mode is 7 bits, even bit, 1 stop bit (7, E, 1). Communication format of RTU

mode is 8

bits, even bit, 1 stop bit (8, E, 1).

C. Function code: 03’H - read data from register. 06’H - write one word into register. 10’H - write multiple

words into register.

Adjust A/D Conversion Curve

Voltage output mode:

Mode 0 of CR#1:

GAIN=5V (2,000

LSB

), OFFSET=0V (0

LSB

).

Mode 1 of CR#1:

GAIN=6V (2,400

LSB

), OFFSET=2V (800

LSB

).

GAIN:

The setting range of voltage output value
when digital input value is K2,000 should be
0

LSB

~ +4,000

LSB

.

OFFSET:

The setting range of voltage output value
when digital input value is K0 should be
-2,000

LSB

~ +2,000

LSB

.

0

+2,000

+4,000

2V

5V

6V

10V

OFFSET

GAIN

voltage
output

Digital input

mode 0

mode 1

GAIN

-OFFSET:

Setting range: +400

LSB

~ +6,000

LSB

.

Current output mode:

Mode 2 of CR#1:

GAIN=12mA (2,400

LSB

), OFFSET=4mA

(800

LSB

).

Mode 3 of CR#1:

GAIN=10mA (2,000

LSB

), OFFSET=0mA

(0

LSB

).nj

GAIN:

The setting range of current output when
digital input value is K2,000 should be 0

LSB

~ +4,000

LSB

.

OFFSET:

The setting range of current output when
digital input value is K0 should be -2,000

LSB

~ +2,000

LSB

.

0

+2,000

+4,000

20mA

OFFSET

GAIN

12mA

10mA

4mA

current
output

digital input

mode 3

mode 2

GAIN

-OFFSET:

Setting range: +400

LSB

~ +6,000

LSB

.

The charts above are D/A conversion characteristic curve of voltage input mode and current input mode. Users
can adjust conversion characteristic curve by changing OFFSET values (CR#22 ~ CR#23) and GAIN values
(CR#28 ~ CR#29) depend on application.

注意事項

請在使用之前,詳細閱讀本使用說明書。

請勿在上電時觸摸任何端子。實施配線,務必關閉電源。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊
意外之外殼配線箱內。另必須具備保護措施 (如: 特殊之工具或鑰匙才可打開) 防止非維護人員操作或意外衝
擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。

輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。

本體上之接地端子

務必正確的接地,可提高產品抗雜訊能力。

產品簡介

說明及週邊裝置

謝謝您採用台達 DVP 系列產品。DVP02DA-S 類比信號輸出模組可透過 DVP-PLC SS/SA/SX/SC/SV 主機程
式以指令 FROM/TO 來讀寫 DVP02DA-S 類比信號輸出模組之資料。而類比信號輸出模組接受來自 PLC 主
機的 2 組 12 位元數位資料,再將數位資料轉換為 2 點類比信號輸出 (電壓或電流皆可)。模組內具有 49 個
CR (Control Register)

暫存器,每個暫存器有 16 bits。

DVP02DA-S

類比信號輸出模組可經由 RS-485 通訊更新韌体版本。電源單元與模組分離,體積小,安裝容

易。

使用者可經由配線選擇電壓輸出或電流輸出。電壓輸出範圍 0V ~ +10V DC (解析度為 2.5mV)。電流輸出範
圍 0mA ~ 20mA (解析度為 5µA)。

產品外觀及各部介紹

90.00

4.00

3.00

25.20

1

2

3

4

60.00

5

6

7

8

9

3

10

FG

V+

I+

COM

C
H
1

FG

V+

I+

COM

C
H
2

11

12

13

3.4

90.00

60.00

3.00

14

尺寸單位:mm

1.

電源、錯誤及運行指示燈

8.

擴充機/擴充模組連接口

2.

機種型號

9.

擴充機/擴充模組固定扣

3. DIN

軌固定扣

10. DIN

軌糟 (35mm)

4.

端子

11. RS-485

通訊口

5.

端子配置

12.

擴充機/擴充模組固定槽

6.

擴充機/擴充模組定位孔

13.

電源輸入口

7.

銘牌

14.

擴充機/擴充模組連接口

繁體中文

外部配線

DC/DC

轉換器

電壓輸出
0V ~ 10V

V+

*2

 

FG

COM

V+

FG

I+

CH1

CH2

24+

24-

AG

+15V

-15V

*3

 

系統接地點

(

接地阻抗100Ω以下)

DC24V

I+

電流輸出
0mA~20mA

COM

CH1

CH2

隔離線 1 

變頻器, 記錄器

比例閥...

接至電源模

組之

隔離線 1 

變頻器, 記錄器

比例閥...

DVP02DA-S

V+

I+

COM

FG
V+

I+

COM

FG

註 1:類比輸出請與其他電源線隔離。
註 2:如果負載之輸入端漣波太大造成配線受雜訊干擾時,請連接 0.1 ~ 0.47µF 25V 之電容。
註 3:請將電源模組之

端及 DVP02DA-S 類比信號輸出模組之

端連接到系統接地點,再將系統接點作第

三種接地或接到配電箱之機殼上。

注意:空端子 請勿配線。

規格

功能規格

數位/類比 (2D/A) 模組

電壓輸出 (Voltage output)

電流輸出 (Current output)

電源電壓

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)

類比訊號輸出通道

2

通道/台

類比輸出範圍

0 ~ 10V

0 ~ 20mA

數位資料範圍

0 ~ 4,000

0 ~ 4,000

解析度

12 bits (1

LS B

=2.5mV)

12 bits (1

LS B

=5µA)

輸出阻抗

0.5Ω or

更低

總和精密度

±0.5% 在 (25°C, 77°F) 範圍內滿刻度時。

±1% 在 (0 ~ 55°C, 32 ~ 131°F) 範圍內滿刻度時。

響應時間

3ms ×

通道數

最大輸出電流

10mA (1KΩ ~ 2MΩ)

容許負載阻抗

0 ~ 500Ω

數位資料格式

16

位元二補數,有效位 11 bits

隔離方式

內部電路與類比輸出端以光耦合器隔離,類比通道間未隔離。

Advertising