Delta Electronics High-speed Counter Module DVP-01HC User Manual

Dvp-01hc, High-speed counter module, Instruction sheet

Advertising
background image

DVP-01HC

High-speed Counter

Module

Instruction Sheet

1

WARNING

Please carefully read this instruction thoroughly prior to use the DVP-01HC.

Make sure that power is OFF before wiring.

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne

dust, humidity, electric shock risk and vibration. Also, it is equipped with protective methods
such as some special tools or keys to open the enclosure, in order to prevent hazard to users
or damage the PLC.

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it

may damage the PLC. Check all the wiring prior to power up.

2

INTRODUCTION


2.1

Model Name Explanation and Peripherals

Thank you for choosing DELTA’s PLC DVP series. DVP-01HC high-speed counter input

module could accept 200KHz pulse from external counter. It uses instruction FROM/TO to
read/write the data in module via EH MPU. There are 33 Controlled Registers (CR, each
register is 16-bit)

in each module. 32 bits data consists of two continuous CRs and allow

executing itself after setting CR.

The different counter modes, such as single-phase mode, two phases mode, 16-bit mode or

32-bit mode, can be designated by CR. The controlled registers are written by instruction TO
via MPU. When wiring, connect 24V, A24+, B24+, P24+, D24+, A12+, B12+, A5+, B5+, P5+
and D5+ to positive potential. In the same way, 0V, A24-, B24-, P24-, D24-, A12-, B12-, A5-,
B5-, P5- and D5- should be connected to negative potential.

Input signal source could be 1-phase or 2-phase encoder and voltage level could be 5V, 12V

and 24V. Besides, it also provides two terminals, PRESET and DISABLE. When terminal
“PRE” is on, the data in CR#10 and CR#11 will be sent to CR#20 and CR#21. That also means
current value of counter will be changed to be factory setting. When terminal “DIS” is on,
“count” operation is disabled.

There are two outputs, YH0 and YH1, in hardware input module of DVP-01HC. When counter

value is equal to the setting, the corresponding output point will activate. The transistors of
output points are independent and isolated.

Nameplate Explanation

24VDC 3W MAX.

0.5 A 5VDC~30VDC 1~10KHz

01HC-H0T4350001

VX.XX

5VDC 12VDC 24

1~200KHz

VDC

Input power supply spec.

Output module spec.

Barcode, serial number and version

Model Name

Input spec.

Model and Serial Number Explanation

Serial Number

Model

for EH series MPU

Product Series

Channel number

Model type

Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model

序號

HC: High-speed counter module

2.2

Product Profile and Outline

1

2

3

4

7

7

5

3

6

10

8

9

Unit: mm

1. DIN rail track (35mm)

2. Mounting wire to connect extension module/extension unit

3. Model name

4. Status Indicator (Power, Run and ERROR)

5. DIN rail clip

6. Terminal

7. Mounting hole

8. Terminal layout

9. Extension port to connect extension module/unit 10. RS-485 communication port

LED Display

1. Power

: Power LED. When external +24V power is applied, it will be ON.

2. L.V.

: Low voltage LED. When external power supply is lower than 19V, it will be ON.

3. UP

: Count up LED

4. DOWN

: Count down LED

5. ψA

: When input point A is ON, it will light.

6. ψB

: When input point B is ON, it will light.

7. PRE

: PRESET LED. When external terminal PRE is ON, it will light.

8. DIS

: DISABLE LED. When external terminal DIS is ON, it will light.

9. YH0, YH1 : When output points YH0 and YH1 are ON, it will light.

2.3

Wiring

To suit M3.5 screw terminals

Below 6.2

Below 6.2

1. Please use O-type or Y-type terminals for I/O wiring terminals. The

specification for the terminals is as shown on the left. Tighten PLC
terminal screws to a torque of 5 to 8 kg-cm (4.3~6.9 in-lbs).

2. I/O signal wires or power supply should not run through the same

multi-wire cable or conduit.

3. Use copper conductor only, 60℃.

External Wiring

4.7K

Shielded wire

A24+

OA

A12+

A5+

A -

B24+
B12+

B5+

B -

2.2K

0.68K

4.7K

2.2K

0.68K

P+24

P+5

PRE-

D+24

D+5

DIS-

4.7K

4.7K

0.68K

4.7K

4.7K

0.68K

OB

PRESET

DISABLE

START

EH MPU

connection
wire

YH0+

YH0-

YH1+

YH1-

+24V

0V

Filter

DC/DC

+24V

+5V

0V

+24V

External Power

DC 12V to 24V

01HC High-speed Counter Module

OUT

OUT

OUT

A phase

B phase

Z phase

+24V

COME

0V

+24V

External Power

DC5V, 12V, 24V

PNP output encoder

Shielded wire

Shielded wire

Shielded wire

Make sure the positive/negative pole of 01HC input terminal wiring is correct when using NPN
encoder.

Start-up current for 01HC is I

PEAK

=0.8A and general working current is I

MAX

=0.2A(input voltage

is +24V).

3

FUNCTION SPECIFICATION

3.1 Function

Specification

1-phase Input

2-phase (A, B) Input

Item

1 Input

2 Inputs

Normal

Frequency

Double

Frequency

Four Times

Frequency

Power Supply

DC24V(-15% ~ +20%), Current consumption 140±30mA
Power is supplied from PLC or external power supply.

Max. Number of Connecting

Units

8 units; (All I/O points are not occupied. There can be 8 special extension units at

most connected to EH series.)

Voltage

Level

Terminals [A24+], [B24+]: DC24V ±10 %
Terminals P24+], [D24+]: DC12V ~24V ±10 %
Terminals [A12+], [B12+]: DC12V ±10 %
Terminals [A5+], [B5+], [P5+], [D5+]: DC5V ±10 %
Choose only one suitable voltage level for positive
pole of each signal.

A: A Phase
B: B Phase
P: Preset
D: Disable

Max. Count

Frequency

200KHz 200KHz 200KHz 100KHz 50KHz

Input

Signal

Waveform

t

3

t

1

t

1

t

2

t

2

t

3

t1: rise/fall time≦0.8us
t2: On/Off pulse width≧2.5us
t3: phase difference between A phase and B
phase ≧1us
PRESET input: input pulse width≧50us
DISABLE input: input pulse width≧50us

Count Mode

There is three count modes: count up/down ((2-phase input for AB phase),
1-phase 2 inputs and 1-phase 1 input.)

Range

32-bit mode: -2,147,483648~+2,147,483,647
16-bit mode: 0~65,536 (upper limit can be set by CR#2,3)

Count

Specification

Comparison

Method

Two comparison values are available and correspond to two outputs, YH0 and
YH1, respectively. When count value is equal to settings, the output will be ON. It
adopts hardware circuit comparison and output settings with real-time handle.

Output

Form

YH0+: output point YH0, transistor: Collector
YH0-: output point YH0, transistor: Emitter
YH1+: output point YH1, transistor: Collector
YH1-: output point YH1, transistor: Emitter

YH0+
YH1+

YH1-

YH0-

Output

Signal

Output

5V TO 30VDC, 0.5A

Connect to DVP-PLC

MPU in Series

The module number it connects to MPU from closest to the farthest is from 0 to
7. 8 modules is the max and it won’t occupy any digital I/O.

3.2 Other

Specification

Environmental specifications

Operation/Storage

1. Operation: 0℃~55℃(Temperature), 50~95%(Humidity), pollution degree 2
2. Storage: -25℃~70℃(Temperature), 5~95% (Humidity)

Vibration/Shock

immunity

Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST
Ea)

Antistatic spec.

All places between terminals and ground comply with the spec.

4

CONTROLLED REGISTER (CR)

DVP-01HC High-speed Counter Module

CR No.

HW LW

Communi

cati

on

Address

Latched

Attr

ibute

Content

Setting Range

#0 H415E

R

Model type

System used, read only, DVP-01HC model code=H’0120

#1 H 415F ╳ R/W

Count
up/down mode
setting

Setting range: 0-1, factory setting K0
1-phase 1 input(Software): count up/down mode setting,
count up: K0, count down:K1

#3 #2 H 4160 ╳ R/W Ring length

16-bit: factory setting is K65,536.

Example:

M0

DTO

K0

K2

K200

K1

Write K200 into first extension module CR#2 and
CR#3 (i.e. CR#3 = 0, CR #2 = 200). Setting
range: K2 to K65,536.

198

199

1

0

0

1

199

198

Count up

Count down

When ring length is set to K200, The count value
will be as shown on the left.

Count up: when count value reaches 199, the
next count value will be 0.

Count down: when count value reaches 0, the
next count value will be 199.

Setting notices:

1. It must write with 32-bit.
2. It only can be write-in when writing value is greater or equal to current count value.
3. It only can be set when counter stops counting and count mode is 16-bit.