Major, minor, and logic programmable alarms, Major, minor, and logic programmable alarms -30, Table 6-13. relay trouble alarms -30 – Basler Electric BE1-851 User Manual
Page 132: Table 6-14. programmable alarms -30
Table 6-13. Relay Trouble Alarms
I.D. #
Name
Description
1
RAM FAILURE
Static RAM read/write error.
2
ROM FAILURE
EPROM program memory checksum error.
3
UP FAILURE
Microprocessor exception or self-test error.
4
EEPROM FATAL ERROR
EEPROM read/write error.
5
ANALOG FAILURE
Analog to digital converter error.
6
CALIBRATION ERR
Relay not calibrated or calibration checksum error.
7
PWR SUPPLY ERR
Power supply out of tolerance.
8
WATCHDOG FAILURE
Microprocessor watchdog circuit timed out.
9
SET DEFLTS LOADED
Relay using setting defaults.
10
CAL DFLTS LOADED
Relay using calibration defaults.
Relay trouble alarms, except for CALIBRATION ERR, EEPROM FATAL ERR, SET DFLTS LOADED, and
CAL DFLTS LOADED indicate that the relay is not functional and causes the self-test diagnostics to force
a microprocessor reset to try to correct the problem.
CALIBRATION ERR, EEPROM FATAL ERROR, or DFLTS LOADED errors indicate that the relay is
functional but needs re-calibration or the setting re-programmed.
Any relay trouble alarm will disable the protection functions, light the Relay Trouble LED, and place the
output contacts in their normal, de-energized state. If a relay trouble (RA-REL) alarm is cleared by
pressing the HMI Reset key while viewing Screen 1.3 or using the RA=0 or RA-REL=0 commands, then
the relay will attempt to return back online by issuing a software reset. The relay resets by going through
a full startup and initialization cycle. If no problems are detected, the relay returns online and enables
protection.
Major, Minor, and Logic Programmable Alarms
The programmable alarms function covers all circuits monitored by the continuous self-test diagnostics
function that does not affect the relay core functions. The alarm function used to monitor the power
system and equipment is part of the programmable alarms. Table 6-14 provides a detailed list of all
programmable alarms. The programmable alarm points can be prioritized into Major and Minor alarms
using the SA-MAJ (setting alarms, major) and SA-MIN (setting alarms, minor) commands. Major alarm
points, when triggered, cause the HMI Major Alarm LED to light and the BESTlogic variable ALMMAJ to
assert. Minor alarm points, when triggered, cause the HMI Minor Alarm LED to light and the BESTlogic
variable ALMMIN to assert.
Table 6-14. Programmable Alarms
I.D. #
Name
Description
1
OUT1 CKT OPEN ALARM ∗
Trip circuit continuity and voltage monitor.
2
BKR FAIL ALARM
Breaker failure trip.
3
RECLOSER FAIL ALARM ∗
Reclose fail timer timed out before breaker closed.
4
RECLOSER LOCKOUT ALARM ∗ Recloser went through sequence without success.
5
BREAKER ALARM 1
Breaker Alarm 1 threshold (SA-BKR1 setting) exceeded.
6
BREAKER ALARM 2
Breaker Alarm 2 threshold (SA-BKR1 setting) exceeded.
7
BREAKER ALARM 3
Breaker Alarm 3 threshold (SA-BKR1 setting) exceeded.
8
P DEMAND ALARM ∗
Phase demand.
9
N DEMAND ALARM ∗
Neutral unbalance demand.
6-30
BE1-851 Reporting and Alarms
9289900990 Rev R