Table 8-21. BUS Contact Sensing Input Logic
Input
Purpose
Name Label
State Labels
Energized De-Energized
IN1 52b Breaker Status.
BREAKER
OPEN
CLOSED
IN2 Block instantaneous
FEEDER_PU
PICKUP
NORMAL
IN3
Signal from relay on bus source that is using
BACKUP logic that a feeder relay is out of
service.
BACKUPMODE BACKUP
NORMAL
IN4
Put the relay in test mode so that reclosing
and breaker failure are disabled when IN4 is
de-energized.
TESTDISABL
NORMAL
TSTMODE
Table 8-22. BUS Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode
Setting
50TP
Used for instantaneous phase overcurrent protection. Block
when feeder relay is picked up indicating that the fault is on a
feeder.
IN2
1 (enabled)
50TN
Used for instantaneous neutral overcurrent protection. Block
when feeder relay is picked up indicating that the fault is on a
feeder.
IN2
1 (enabled)
50TQ
Used for instantaneous negative-sequence overcurrent
protection. Block when feeder relay is picked up indicating
that the fault is on a feeder.
IN2
1 (enabled)
150TP
N/A
0
0 (disabled)
150TN
N/A
0
0 (disabled)
150TQ
N/A
0
0 (disabled)
51P
Used for timed phase overcurrent protection.
0
1 (enabled)
51N
Used for timed neutral overcurrent protection.
0
1 (enabled)
51Q
Used for timed negative-sequence overcurrent protection.
0
1 (enabled)
62
Initiate time delay when 51 trip expressions are TRUE to
provide backup tripping of the bus breaker when the relay is
being used for backup feeder protection.
VO8
1 (PU/DO)
162
N/A
0
0 (disabled)
79
N/A
0
0 (disabled)
BF
N/A
0
0 (disabled)
GROUP
Switch to setting group 1 if feeder relay is out of service.
IN3
2(Binary
Inputs)
No manual logic is used.
0
No manual logic is used.
0
No manual logic is used.
0
Fix Auto/Manual switch in the manual position only. Selection
by contact sensing only. No automatic selection logic.
0