Dataprobe iPIO-8 Quick Start User Manual

Overview, Hardware installation, Ipio-8

Advertising
background image

Technical Support:

Main:

201-934-5111
201-934-9944

[email protected]
Website: dataprobe.com

Download the complete iPIO-8 Installation and Operation manual as well as the latest firmware and any
utilities at:

http://dataprobe.com/ipio8-web-relay-control.html?Support

Overview


The iPIO-8 is a network attached, IP addressed digital input and output device. The iPIO-8 can be
controlled and monitored with a standard web browser. Multiple iPIO-8 devices can communicate
amongst themselves to transport I/O information across the network. Each iPIO-8 has eight controllable
form C relays, and eight digital inputs.

Hardware Installation

Inputs

Connect the inputs to the iPIO-8 using the removable
screw terminals. Connect only dry contact closures; relay
or switch contacts. Connect one leg to the G terminal and
the other to the + terminal.

For information on connecting wet contacts, consult the
complete manual before making any connections.

Relays

Connect to the iPIO-8 relays using the removable screw
terminals. Relays are Form C. Connect to the Common
(C), Normally Closed (NC) and Normally Open (NO) as
marked. When the iPIO-8 relay is in the Open Condition,
the Common is connected to the Normally Open. In the
Closed state, the Common and Normally Closed are
connected.

Relay Specifications

Rating (resistive)

0.5 A 120 VAC or 1 A 24 VDC

Maximum Carrying Current

2 A

Maximum Switching Power

60 AV, 24 W

Maximum Switching Voltage

120 VAC/60 VDC

Maximum Switching Current

1A

Life Expectancy

5 Million Operations Mechanical.
100K Operations at rated load


iPIO-8

Ethernet I/O Monitor and Control

Quick Start Guide

Advertising