Repair Section

80

8.2 Removal of Refrigeration System Components

WARNING

• Before replacing any refrigeration cycle component, recover the refrigerant using

standard recovery procedures and equipment.

• When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)

and high pressure side (tube 2) as shown in the figure below.

CAUTION

• To prevent oxidation, dry nitrogen should be conducted {flow rate 0.27 gal/min (1 L/min)} through

the pinch-off tube during any brazing operation.

• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,

to protect them from the flame.

< NOTE >

When replacing the compressor, attach the pipe 1 and the pipe 2 packaged in the compressor

assembly.

ILL00668-00

F

E

G

J

Pipe 2

Pipe 1

Tube 1

Tube 2

H

D

C

B

Part to Replace
• Compressor
• Condenser
• Electronic Expansion Valve
• Evaporator

Disconnect at

E, F, G, H

B, C

• High Pressure Switch

J

C, D

A, I

I

A