Technical Specifications - Table 2

ITEM

SPECIFICATIONS

Ventilation Equipment for
Indoor Coil

Type of Indoor Coil (Heat Exchanger)

Plate Fin

Type of Fan

Centrifugal Fan

Air Flow

High

540 CFM (918 m

3

/h)

Medium

440 CFM (748 m

3

/h)

Low

350 CFM (595 m

3

/h)

Max. External Static Pressure

0.31 IWG (77 Pa)

Motor Output

High

0.12 kW

Medium

0.045 kW

Low

0.017 kW

Power Cord

NEMA Plug Configuration

5-20

Gage x Length

12 AWG (3-core) x 10 ft (3.0 m)

Refrigerant

Refrigerant Control

Electronic Expansion Valve

Type

R-410A

Amount

1.94 lb (0.88 kg)

Signal Connection

Fire Alarm Input 1 (FA-1, FA-2)

• No-voltage contact input
• Contact resistance less than 100

ohm

Fire Alarm Input 2 (Al-1, Al-2)

Warning Signal Output (OS-1, OS-2)

2 A at 30 V (DC/AC) max. with resis-

tive load

External Wall Thermostat

Millivolt Type

With terminals RC, O/B, G, Y

24VAC Type

With terminals C, O/B, G, Y,

24VAC RC/RH

Dimension

W x D x H

21 x 27 x 50 in

(533 x 686 x 1,270 mm)

Weight

Net

214 lb (97 kg)

Shipping

250 lb (113 kg)

Drain Tank Capacity

5.0 gal (19 L)

Cooling Operating Condition
Range

Inlet Air Temperature

Max.

95 °F (35 °C), 60 %RH

Min.

65 °F (18 °C), 50 %RH

Heating Operating Condition
Range

Without Outdoor Heat
Exchanger Duct

Max.

80 °F (26.7 °C), 50 %RH

Min.

40 °F (4.4 °C), 50 %RH

With Outdoor Heat
Exchanger Duct

Max.

80 °F (26.7 °C), 50 %RH

Min.

Indoor Heat Exchanger:

40 °F (4.4 °C), 50 %RH

Outdoor Heat Exchanger:

24 °F (-4.4 °C), 50 %RH