Technical Specifications - Table 2
ITEM
SPECIFICATIONS
Ventilation Equipment for
Indoor Coil
Type of Indoor Coil (Heat Exchanger)
Plate Fin
Type of Fan
Centrifugal Fan
Air Flow
High
540 CFM (918 m
3
/h)
Medium
440 CFM (748 m
3
/h)
Low
350 CFM (595 m
3
/h)
Max. External Static Pressure
0.31 IWG (77 Pa)
Motor Output
High
0.12 kW
Medium
0.045 kW
Low
0.017 kW
Power Cord
NEMA Plug Configuration
5-20
Gage x Length
12 AWG (3-core) x 10 ft (3.0 m)
Refrigerant
Refrigerant Control
Electronic Expansion Valve
Type
R-410A
Amount
1.94 lb (0.88 kg)
Signal Connection
Fire Alarm Input 1 (FA-1, FA-2)
• No-voltage contact input
• Contact resistance less than 100
ohm
Fire Alarm Input 2 (Al-1, Al-2)
Warning Signal Output (OS-1, OS-2)
2 A at 30 V (DC/AC) max. with resis-
tive load
External Wall Thermostat
Millivolt Type
With terminals RC, O/B, G, Y
24VAC Type
With terminals C, O/B, G, Y,
24VAC RC/RH
Dimension
W x D x H
21 x 27 x 50 in
(533 x 686 x 1,270 mm)
Weight
Net
214 lb (97 kg)
Shipping
250 lb (113 kg)
Drain Tank Capacity
5.0 gal (19 L)
Cooling Operating Condition
Range
Inlet Air Temperature
Max.
95 °F (35 °C), 60 %RH
Min.
65 °F (18 °C), 50 %RH
Heating Operating Condition
Range
Without Outdoor Heat
Exchanger Duct
Max.
80 °F (26.7 °C), 50 %RH
Min.
40 °F (4.4 °C), 50 %RH
With Outdoor Heat
Exchanger Duct
Max.
80 °F (26.7 °C), 50 %RH
Min.
Indoor Heat Exchanger:
40 °F (4.4 °C), 50 %RH
Outdoor Heat Exchanger:
24 °F (-4.4 °C), 50 %RH