Operation Section

47

6.3 Warning Device Connection (Field Supplied)

• The controller of this unit is equipped with a warning signal output relay which can be used to

monitor failure condition of the unit and is compatible with various external warning devices such
as alarm speaker, light indicators, etc.

Specifications:

- Relay type: Form C, normal open dry contact
- Relay output contactor rating: 2 A at 30 V (DC/AC) maximum with resistive load

WARNING

Disconnect power before installation. Beware that some residual voltage may remain in
the unit immediately after the power is disconnected.

1) Turn the unit off and unplug the power cord.

Take out seven (7) screws and remove the
service panel from rear of the unit.

2) Squeeze the inner latches and push out the

black cap from inside the panel.
Insert the warning signal wires through the hole
in the rear panel.

Recommended wire size:

- 16 AWG ~ 22 AWG

Screws (7)

Cap

ILL00806-00

ILL00046-01

Latch

Cap