8 condensate pump kit (optional), 10 compressor protection, 11 temperature control – MovinCool Climate Pro 18 Service Manual User Manual
Page 41: Condensate pump kit (optional), Compressor protection, Temperature control
Operation Section
41
(1) How to re-start the unit
• Press the START/STOP button on the control panel. The unit returns to the previous operation mode.
5.8 Condensate Pump Kit (Optional)
• The Climate Pro 18 model comes standard with a drain tank, which collects the water that forms
on the heat exchangers during normal operation. If the unit is required to operate continuously
without periodically emptying this tank, a condensate pump may be needed. A condensate
pump kit is available for this model.
5.9 Automatic Restart after Power Interruption (Automatic Recovery Feature)
• The program within the microprocessor of the Climate Pro 18 contains a feature that
automatically restarts the unit after power is lost and regained. The unit returns to the same
operation mode as it was prior to the loss of power. Any preset program is retained in the
memory in the event power loss occurs.
5.10 Compressor Protection
• There is a time delay program within the microprocessor. This prevents a heavy load from being
applied on the compressor motor when restarting the unit cool or heat mode after a very short
period of time. This delay is in effect any time when the compressor is turned on by selection of
the cool or heat mode operation. temperature set point (thermostatic control), power interruption
restart or condensate pump (optional) operation.
Specifications:
Time delay
- 120 ± 20 sec.
5.11 Temperature Control
• The compressor operation during cool or heat mode operation is controlled by the
microprocessor which receives input signals from the RTS (indoor air inlet thermistor) and the
setting of the temperature set point. The temperature set point (desired room temperature) can
be adjusted by pressing the TEMP+ or -TEMP button on the control panel. The adjustment
range of the temperature set point is:
For cool mode:
- 65 °F ~ 90 °F (18 °C ~ 32 °C)
For heat mode:
- 55 °F ~ 80 °F (13 °C ~ 27 °C)