13  Directory of the Parameters in Installer Mode and Expert Mode

Operating Manual

SI30M-44M-60H-80H-BE-en-30

109

233# Grid Start, for off-grid systems only

232.54 PF-PFStop

Displacement power

factor cos φ at the end

point at PFCtlW (expert

mode, protected by

SMA Grid Guard)

0.8 to 1.0

✓ ✓ 0.9

232.55 PF-PFExtStop

Excitation type at the end

point at PFCtlW (expert

mode, protected by

SMA Grid Guard)

OvExt

Lagging

✓ ✓ UnExt

UnExt

Leading

232.56 PF-WNomStop Proportion of the

maximum active power

at the end point in % at

PFCtlW (expert mode,

protected by

SMA Grid Guard)

232.52

PF-WNomStr to

100%

✓ ✓ 100%

232.58 GdAIFac

Anti-islanding factor in

current-controlled grid

operation with I-Loop

(expert mode)

0.00 to 3.00

✓ ✓ 0.50

232.59 MsPhSel

Line conductor to which

the Sunny Island is

connected (expert mode)

L1

Line conductor L1

✓ ✖ −

L2

Line conductor L2

L3

Line conductor L3

232.60 EZATyp

Type of PV system feed-in

(expert mode)

Asymmetric

At least one PV

inverter is

single-phase and

feeds in

asymmetrically.

✓ ✖ −

Symmetric

All PV inverters are

three-phase and

feed in

symmetrically.

No.

Name

Description

Value

Explanatio

n

Default

value

233.01 GdSocEna

Enable grid request

based on SOC

(expert mode)

Disable

Disable

✖ ✓ Disable

Enable

Enable

233.02 GdSocTm1Str

SOC threshold for

connection to the utility

grid in interval 1 in %

(expert mode)
Interval 1 begins at time

233.06 GdTm1Str.

1% to

233.03 GdSocTm1Stp

✖ ✓ 40%

No.

Name

Description

Value

Explanation

Default

value