13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
109
233# Grid Start, for off-grid systems only
232.54 PF-PFStop
Displacement power
factor cos φ at the end
point at PFCtlW (expert
mode, protected by
SMA Grid Guard)
0.8 to 1.0
‒
✓ ✓ 0.9
232.55 PF-PFExtStop
Excitation type at the end
point at PFCtlW (expert
mode, protected by
SMA Grid Guard)
OvExt
Lagging
✓ ✓ UnExt
UnExt
Leading
232.56 PF-WNomStop Proportion of the
maximum active power
at the end point in % at
PFCtlW (expert mode,
protected by
SMA Grid Guard)
232.52
PF-WNomStr to
100%
‒
✓ ✓ 100%
232.58 GdAIFac
Anti-islanding factor in
current-controlled grid
operation with I-Loop
(expert mode)
0.00 to 3.00
−
✓ ✓ 0.50
232.59 MsPhSel
Line conductor to which
the Sunny Island is
connected (expert mode)
L1
Line conductor L1
✓ ✖ −
L2
Line conductor L2
L3
Line conductor L3
232.60 EZATyp
Type of PV system feed-in
(expert mode)
Asymmetric
At least one PV
inverter is
single-phase and
feeds in
asymmetrically.
✓ ✖ −
Symmetric
All PV inverters are
three-phase and
feed in
symmetrically.
No.
Name
Description
Value
Explanatio
n
Default
value
233.01 GdSocEna
Enable grid request
based on SOC
(expert mode)
Disable
Disable
✖ ✓ Disable
Enable
Enable
233.02 GdSocTm1Str
SOC threshold for
connection to the utility
grid in interval 1 in %
(expert mode)
Interval 1 begins at time
233.06 GdTm1Str.
1% to
233.03 GdSocTm1Stp
‒
✖ ✓ 40%
No.
Name
Description
Value
Explanation
Default
value