9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

57

9.4.5 Utility Grid Category (5xx)

9.4.6 Relay Category (6xx)

W 402 GnFailLock

1

Connection of the

generator is locked as a

result of too many

interrupted start

processes.

• Ensure that the generator triggering is functioning,

the generator starts, and there is constant and stable

generator voltage present at connection AC2.

• To re-enable connection of the generator,

acknowledge the generator error (see Section 9.2

"Acknowledging Errors", page 42).

A warm-up time 234.12 GnWarmTm that is too short

may have been configured and hence the generator is

unable to supply valid voltage.

• Ensure that the generator warm-up time is configured

appropriately (see the Sunny Island inverter

installation manual).

No.

Name

Level Cause

Corrective measures

W 501 GdRevPwrProt

1

AC sources in the stand-alone grid are

performing undesired feed-in to the utility

grid. The reverse power to the utility grid has

been exceeded for too long.

• Contact the SMA Service

Line, if required.

W 502 GdRevPwrProtSL1

1

W 503 GdRevPwrProtSL2

1

W 505 GdCurNomExceed 1

The feed-in current of the master is greater

than 232.04 GdCurNom.

• Contact the SMA Service

Line, if required.

W 506 GdCurNomExcSlv1 1

The feed-in current of slave 1 is greater than

232.04 GdCurNom.

W 507 GdCurNomExcSlv2 1

The feed-in current of slave 2 is greater than

232.04 GdCurNom.

No.

Name

Level Cause

Corrective measures

F 605 TransfNotOpn

4

Internal transfer relay in the

master does not open.

A bypass switch may have bridged the internal

transfer relay.

• Ensure that the bypass switch is in the

position for operation with the

Sunny Island.

Ensure that the connections AC1 and

AC2 are not bridged.

W 606 TransfNotOpnSL1 1

Internal transfer relay in

slave 1 does not open.

W 607 TransfNotOpnSL2 1

Internal transfer relay in

slave 2 does not open.

No.

Name

Level Cause

Corrective measures