0 system data, Ystem, Table 2 – Emerson Liebert Challenger ITR User Manual

Page 32: Liebert challenger itr air-cooled data—60 hz

Advertising
background image

System Data

24

13.0 S

YSTEM

D

ATA

Table 2

Liebert Challenger ITR air-cooled data—60 Hz

System Type

BR = Horizontal Flow

Self-Contained

Split Systems

w/Outdoor Prop-Fan

Condensing Unit

w/Indoor Centrifugal

Condensing Unit

Indoor Unit

BR 067A

BR 060E

BR 060E

Net Capacity Data

BTU/H

kW

BTU/H

kW

BTU/H

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

Total

78,100

22.9

76,200

22.3

73,200

21.4

Sensible

78,100

22.9

76,200

22.3

73,200

21.4

Non Standard Flow Rates

2400 CFM

2300 CFM

2100 CFM

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

Total

77,500

22.7

75,800

22.2

73,000

21.4

Sensible

77,500

22.7

75,800

22.2

73,000

21.4

Non Standard Flow Rates

2700 CFM

2500 CFM

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

Total

73,600

21.6

72,400

21.2

70,600

20.7

Sensible

73,600

21.6

72,400

21.2

70,600

20.7

85°F DB, 64.4°F WB (29.4°C DB, 18

°

C WB) 32% RH

Total

69,700

20.4

68,400

20.0

66,800

19.6

Sensible

69,700

20.4

68,400

20.0

66,800

19.6

80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH

Total

66,000

19.3

64,400

18.9

63,100

18.5

Sensible

66,000

19.3

64,400

18.9

63,100

18.5

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

Total

66,900

19.6

65,300

19.1

63,800

18.7

Sensible

54,600

16.0

54,000

15.8

53,400

15.6

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH

Total

62,700

18.4

60,800

17.8

59,600

17.5

Sensible

53,000

15.5

52,300

15.3

51,800

15.2

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

Total

61,200

17.9

60,700

17.8

59,600

17.5

Sensible

57,000

16.7

60,700

17.8

59,600

17.5

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

Total

60,200

17.6

58,200

17.1

57,200

16.8

Sensible

52,000

15.2

51,200

15.0

50,700

14.9

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

Total

58,900

17.3

58,400

17.1

57,500

16.8

Sensible

55,800

16.3

58,400

17.1

57,500

16.8

Fan Data (Blower A12x9AT)**

Standard Air, CFM (CMH)

2800 (4760)

2800 (4760)

2800 (4760)

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

1-1/2 (1.1)

1-1/2 (1.1)

Opt Fan Motor, hp (kW)

2 (1.5)

2 (1.5)

2 (1.5)

Ext Static, in. WG (Pa)

.3 (75)

.3 (75)

.3 (75)

Evaporator Coil (V-FRAME, at standard conditions)

Face Area, ft.

2

(m

2

)

6.67 (.62)

6.67 (.62)

6.67 (.62)

Rows

4

4

4

Face Velocity - FPM (m/s)

405 (2.1)

405 (2.1)

405 (2.1)

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

Capacity, inc. motor heat, BTU/H (

element

kW)

56,200 (15)

56,200 (15)

56,200 (15)

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)

Capacity, inc. motor heat, BTU/H (kW)

88,700 (26.0)

88,700 (26.0)

88,700 (26.0)

Flow Rate - GPM (l/s)

5.0 (.32)

5.0 (.32)

5.0 (.32)

Pressure drop - ft. (kPa)

16.9 (50.4)

16.9 (50.4)

16.9 (50.4)

* The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the

standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%.

** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for

recommendations.