background image

Electrical Data

47

Table 23

Fan speed control condensers *

95°F (35°C) Ambient, 1 Phase - 60 Hz

CSF104

Voltage

208/230

460

575

FLA

4.8

2.5

1.9

WSA

6.0

3.1

2.4

OPD

15.0

15.0

15.0

* Contact factory for 380-3-60 data.

Table 24

Liebert Lee-Temp condensers *

95°F (35°C) Ambient, 3 Phase - 60 Hz

CSL104

Voltage

208/230

460

575

FLA

3.5

1.7

1.4

WSA

4.4

2.1

1.8

OPD

15.0

15.0

15.0

* Contact factory for 380-3-60 data.

Table 25

Liebert Lee-Temp receiver heater pads for use w/CSL condensers

Volts

120

230

Watts/Pad

150

150

FLA

1.4

0.7

WSA

1.8

0.9

OPD

15

15

Separate electrical source required for continuous operation
of single phase heater pads for Liebert Lee-Temp.

Table 26

Drycooler and pump package - 95°F (35°C) ambient *

Voltage

208/230

460

575

Glycol
DSF Model

112

112

112

Pump Hp

3/4

3/4

3/4

FLA

7.0

3.3

2.7

WSA

7.9

3.7

3.1

OPD

15

15.0

15.0

Glycol DS0174
DSF Model

174

174

174

Pump Hp

1.5

1.5

1.5

FLA

13.6

6.4

5.2

WSA

15.3

7.2

5.8

OPD

20

15.0

15.0

GLYCOOL
DSO Model

112

112

112

Pump Hp

1-1/2

1-1/2

1-1/2

FLA

10.1

4.7

3.8

WSA

11.8

5.5

4.4

OPD

15

15

15

1. Pump and drycooler powered from same 3 phase feeder.
* Contact factory for 380-3-60 data.

Advertising