Table 10

Liebert Challenger ITR glycol cooled data, 60 Hz

System Type

BR = Horizontal Flow

BM = Horizontal Flow with Econ-O-Coil

Glycol Cooled

GLYCOOL

Self-Contained

Split Systems

Self Contained

Indoor Unit

BR 071WG

BR 060E

BM 061G

Net Capacity Data

BTU/H

kW

BTU/H

kW

BTU/H

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

Total

69,800

20.5

71,600

21.0

66,000

19.3

Sensible

69,800

20.5

71,600

21.0

66,000

19.3

Non Standard Flow Rates

1800 CFM, 21.5 GPM,

27.4 FT PD

2100 CFM

2600 CFM, 20.5 GPM,

24.6 FT PD

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

Total

68,600

20.1

72,300

21.2

64,700

19.0

Sensible

68,600

20.1

72,300

21.2

64,700

19.0

Non Standard Flow Rates

2100 CFM, 21.5 GPM,

27.4 FT PD

2600 CFM

2300 CFM, 19.5 GPM,

22.5 FT PD

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

Total

64,700

19.0

69,900

20.5

65,300

19.1

Sensible

64,700

19.0

69,900

20.5

65,300

19.1

Non Standard Flow Rates

2100CFM,18.5 GPM, 20.9FT PD

19.5 GPM, 22.5 FT PD

85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH

Total

62,800

18.4

66,200

19.4

61,500

18.0

Sensible

62,800

18.4

66,200

19.4

61,500

18.0

Non Standard Flow Rates

2300 CFM

80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH

Total

62,400

18.3

62,500

18.3

58,200

17.1

Sensible

62,400

18.3

62,500

18.3

58,200

17.1

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

Total

62,900

18.4

63,000

18.5

59,900

17.6

Sensible

53,200

15.6

53,200

15.6

51,200

15.0

75

°F

DB, 62.5

°F

WB (23.9

°C

DB, 16.9

°C

WB) 50% RH

Total

58,900

17.3

58,800

17.2

55,900

16.4

Sensible

51,500

15.1

51,500

15.1

49,500

14.5

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

Total

59,000

17.3

59,000

17.3

55,000

16.1

Sensible

59,000

17.3

59,000

17.3

55,000

16.1

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

Total

56,500

16.6

56,500

16.6

53,600

15.7

Sensible

50,500

14.8

50,500

14.8

48,500

14.2

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

Total

56,900

16.7

56,900

16.7

53,000

15.5

Sensible

56,900

16.7

56,900

16.7

53,000

15.5

GLYCOOL Coil Sensible Capacity
75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 45°F (7.2°C) EGT

47,700

14.0

Fan Data (Blower A12x9AT)**

Standard Air, CFM (CMH)

2800 (4760)

2800 (4760)

2800 (4760)

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

1-1/2 (1.1)

2 (1.5)

Opt Fan Motor, hp (kW)

2 (1.5)

2 (1.5)

N/A

Ext Static, in. WG (Pa)

.3 (75)

.3 (75)

.3 (75)

Evaporator Coil (V-Frame, at standard conditions)

Face Area, ft.

2

(m

2

)

6.67 (.62)

6.67 (.62)

6.67 (.62)

Rows

4

4

4

Face Velocity, FPM (m/s)

405 (2.1)

405 (2.1)

405 (2.1)

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

Capacity, inc. motor heat, BTU/H(element kW)

56,200 (15)

56,200 (15)

57,700 (15)

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes standard air volume and optional fan motor hp)

Capacity, inc. motor heat, BTU/H(kW)

88,700 (26.0)

88,700 (26.0)

N/A

Flow Rate, GPM (l/s)

5.0 (.32)

5.0 (.32)

5.0 (.32)

Pressure drop, ft. (kPa)

16.9 (50.4)

16.9 (50.4)

16.9 (50.4)

Hot Gas Reheat - Optional (includes standard air volume and optional fan motor)
Capacity, inc. motor heat, BTU/H (kW)

54,900 (16.1)

54,900 (16.1)

N/A

*

The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for

ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%. All above data is based on 40% ethylene glycol solution.

** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.