5204SE-MNET-PDPMV1 ♦ ProLinx Gateway

Reference

Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master

User Manual


Page 116 of 235

ProSoft Technology, Inc.

December 22, 2009

DFB Acyclic Mailbox Message: Set Operating Mode - M340

This command allows setting the operating mode of the PROFIBUS Master
(STOP, CLEAR, or OPERATE).

MNETDPV1_MAILVAR_SetOperateMode Variables - M340

This variable structure is the one to use with your control and sequencing logic
when you want to send a request to set the PROFIBUS Master/network
operating mode. Possible choices are:

ƒ Operate - Tells the PROFIBUS Master to begin and continue normal cyclic

polling and pass acyclic messages, if requested. The network should be in
Stop mode when you issue this command message.

ƒ Stop - Tells the PROFIBUS Master to interrupt normal cyclic polling. Acyclic

messaging can still be accomplished when the network is stopped. The
network should be in Operate mode when you issue this command.

ƒ Clear - Tells the PROFIBUS Master to attempt to clear diagnostic errors and

re-initialize the PROFIBUS network. The network should be in Stop mode
when you issue this command.