Heat exchanger unit (hex) with coupler, Removing the heat exchanger unit with couplers, Sps–heat exchanger – HP 403349-003 User Manual

Page 59: Heat exchanger, Unit (hex) with coupler

Advertising
background image

Removal and replacement procedures 59

Heat exchanger unit (HEX) with coupler

The three heat exchanger units are located on the front of the MCS unit.
You can replace the HEX units during operation.

The following tools are required for installation:

T-25 Torx driver

Water hose fitting wrench (included with your original MCS unit)

Counter hold wrench (included with your original MCS unit)

Removing the heat exchanger unit with couplers

NOTE:

For this procedure, remove the fan unit seated directly behind the heat exchanger unit

you will remove.

1.

Remove the fan unit ("

Removing the fan unit

" on page

51

).

2.

Remove the air deflector plate ("

Removing the air deflector plate

" on page

33

).

NOTE:

The heat exchanger units are deep-seated within the MCS unit. To access the

connections described in the following steps, extend your arm inside the MCS unit until you
come in contact with the appropriate connectors.