Setting g.soak (guarantee soak) items – Honeywell DCP552 Mark II User Manual
Page 148
8-13
■
Setting G.SOAK (Guarantee soak) items
(1) In the set value display state, move to the G.SOAK item to be set for the
segment on the programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first
setting).
(3) Use the
↑, ↓, ←, and →
keys
to make the first setting – setting the G.SOAK
type.
Setting range: 0 to 3
0: No G.SOAK
1: First G.SOAK segment
2: Last G.SOAK segment
3: Entire G.SOAK segment
(4) Press the
ENTER key
to stop the flashing on display panel 1 and display
panel 2 starts flashing. (Start of second setting)
Note, however, that when the first setting is 0, “-----” is shown in the second
panel which does not flash.
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to
unset state “
g.S.0/
-----” and the flashing stops.)
(5) Use the
↑, ↓, ←, and →
keys
to make the second setting (G.SOAK width).
Setting range: 0 to 1000 SPU
(6) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to
unset state “
g.S.0/
-----” and the flashing stops.)
●
Display
•
Unset values are indicated as “
g.S.0/
-----”.
•
When setup data
C59
is set to 1, a G.SOAK item on the programming map is
skipped and not displayed.
NOTE
When a G.SOAK setting is something other than 0, it uses a subfunction.
A subfunction cannot be used when a setting has not been made “
g.S.0/
-----”.
PROG
SEG
PROFILE
Program
number
Segment
number
Set G.SOAK type value
Pattern trend
G. SOAK TYPE
BAND
Set G.SOAK width value
Chapter 8. PROGRAM SETUP