Calibration Procedures

Enter calibration mode

(1)

Release keylock. (

PARA PA01=0

)

(2)

Press

DISP key

to permit ordinary indication condition.

Change to READY (

RUN

and

HLD

are off) and AUTO (

MAN

off) modes.

The following LEDs will illuminate after the above operations.

RUN

LED is OFF

HLD

LED is OFF

MAN

LED is OFF

Figure 12-2.

(3)

To enter calibration mode, hold down the

FUNC key

, and press

SETUP key

and

ENTER key

simultaneously.

The display will show the symbols described in Figure 12-3. If the indication

is different, repeat the above procedure after pushing

DISP key

to refresh the

display.

(4)

To select individual calibration items, press

,

,

,

, keys

to select the

item by scrolling, then

SETUP key

, and

ENTER key

.

The order of calibration items is described in Table 12-2.

Figure 12-3.

FUNC

AT

SETUP

ENTER

A/M

PID

PARA

CLR

CARD

LOAD

SAVE

LOADER

CYC

OUT

DEV

PV

SP

TM

SYN

RUN

HLD

MAN
PRG

AT

BAT
EG1
EG2

PROG RUN/HOLD DISP

RESET

PROG

SEG

PROFILE

MESSAGE

MESSAGE

ADV

0.0.0.0.

A.d.J.S.

00

00

FUNC

AT

SETUP

ENTER

A/M

PID

PARA

CLR

CARD

LOAD

SAVE

LOADER

CYC

OUT

DEV

PV

SP

TM

SYN

RUN

HLD

MAN
PRG

AT

BAT
EG1
EG2

PROG RUN/HOLD DISP

RESET

PROG

SEG

PROFILE

MESSAGE

MESSAGE

ADV

Upper Display

Lower Display

PROG Display

(Program No. Display)

SEG Display

(Segment No. Display)

12-7

Chapter 12. CALIBRATION

Advertising